PACi standard, Gainable haute pression statique • R410A

The ducted systems are the ideal solution for flexible, concealed air conditioning and the optional 200 mm spigots ensure simple, hassle-free connection to spiral ductwork.

  • High ESP (external static pressure) up to 150 Pa
  • Automatic learning function for the required static pressure on site during commissioning (a standard wired remote controller is required)
  • DC FAN for better efficiency and control
  • Built in drain pump
  • Datanavi simple support tool App with remote controller (CZ-RTC5B)
  • Twin split options
  • Easy connection and control of external fan or ERV using the connector PAW-FDC on the indoor unit PCB. The external device can be controlled by the remote control of the Panasonic indoor unit

Caractéristiques

Voir tout
PACi standard, Gainable haute pression statique • R410A Monophasé Triphasé
60 kW 71 kW 100 kW 125 kW 100 kW 125 kW 140 kW
EER (Nominal) (1) W/W 3,35 (5,97 - 2,85) A 2,76 (5,97 - 2,48) D 3,01 (5,09 - 2,74) B 3,05 (4,22 - 2,70) B 3,01 (5,09 - 2,74) B 3,05 (4,22 - 2,70) B 3,22 (3,93 - 2,58) A
COP (Nominal) (1) W/W 4,38 (6,32 - 4,12) A 4,10 (6,32 - 3,68) A 3,80 (5,12 - 3,45) A 3,82 (4,66 - 3,41) A 3,80 (5,12 - 3,45) A 3,82 (4,66 - 3,41) A 3,91 (4,56 - 3,08) A
Kit KIT-60PFY1E5D KIT-71PFY1E5D KIT-100PFY1E5D KIT-125PFY1E5D KIT-100PFY1E8D KIT-125PFY1E8D KIT-140PFY1E8D
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity (Nominal) kW 6,00 7,10 10,00 12,50 10,00 12,50 14,00
Cooling capacity (Min) kW 2,00 2,00 2,70 3,80 2,70 3,80 3,30
Cooling capacity (Max) kW 7,10 7,70 11,50 13,50 11,50 13,50 15,50
EER (Nominal) (1) W/W 3,35 2,76 3,01 3,05 3,01 3,05 3,22
EER (Min) (1) W/W 5,97 5,97 5,09 4,22 5,09 4,22 3,93
EER (Max) (1) W/W 2,85 2,48 2,74 2,70 2,74 2,70 2,58
SEER (2) 5,50 A 5,40 A 5,40 A 5,11 5,20 A 5,10 5,31
Pdesign (cooling) kW 6,00 7,10 10,00 12,50 10,00 12,50 14,00
Input power cooling (Nominal) kW 1,79 2,57 3,32 4,10 3,32 4,10 4,35
Input power cooling (Min) kW 0,34 0,34 0,53 0,90 0,53 0,90 0,84
Input power cooling (Max) kW 2,49 3,10 4,20 5,00 4,20 5,00 6,00
Annual energy consumption cooling (3) kWh/a 382 460 648 673
Heating capacity (Nominal) kW 6,00 7,10 10,00 12,50 10,00 12,50 14,00
Heating capacity (Min) kW 1,80 1,80 2,10 3,40 2,10 3,40 4,10
Heating capacity (Max) kW 7,00 8,10 13,80 15,00 13,80 15,00 16,00
Heating capacity at -7°C (2) kW 11,00 11,00 12,32
Heating capacity at -15°C (2) kW
COP (Nominal) (1) W/W 4,38 4,10 3,80 3,82 3,80 3,82 3,91
COP (Min) (1) W/W 6,32 6,32 5,12 4,66 5,12 4,66 4,56
COP (Max) (1) W/W 4,12 3,68 3,45 3,41 3,45 3,41 3,08
SCOP (2) 4,00 A+ 4,00 A+ 3,80 A 3,60 3,80 A 3,60 3,53
Pdesign at -10°C kW 6,00 6,00 9,50 12,50 9,50 12,50 14,00
Input power heating (Nominal) kW 1,37 1,73 2,63 3,27 2,63 3,27 3,58
Input power heating (Min) kW 0,29 0,29 0,41 0,73 0,41 0,73 0,90
Input power heating (Max) kW 1,70 2,20 4,00 4,40 4,00 4,40 5,20
Annual energy consumption heating (3) kWh/a 2100 2100 3500 3500
Indoor unit S-60PF1E5B S-71PF1E5B S-100PF1E5B S-125PF1E5B S-100PF1E5B S-125PF1E5B S-140PF1E5B
External static pressure (Nominal) (5) Pa 70 70 100 100 100 100 100
External static pressure (Min) (5) Pa 10 10 10 10 10 10 10
External static pressure (Max) (5) Pa 150 150 150 150 150 150 150
Indoor air flow (Hi) m³/min 21,00 21,00 32,00 34,00 32,00 34,00 36,00
Indoor air flow (Med) m³/min 19,00 19,00 26,00 29,00 26,00 29,00 32,00
Indoor air flow (Lo) m³/min 15,00 15,00 21,00 23,00 21,00 23,00 25,00
Indoor sound pressure (Hi) (6) dB(A) 35 35 38 39 38 39 40
Indoor sound pressure (Med) (6) dB(A) 32 32 34 35 34 35 36
Indoor sound pressure (Lo) (6) dB(A) 26 26 31 32 31 32 33
Indoor dimension (Height) mm 290 290 290 290 290 290 290
Indoor dimension (Width) mm 1000 1000 1400 1400 1400 1400 1400
Indoor dimension (Depth) mm 700 700 700 700 700 700 700
Indoor net weight kg 33 33 45 45 45 45 45
Outdoor unit U-60PEY2E5 U-71PEY2E5 U-100PEY1E5 U-125PEY1E5 U-100PEY1E8 U-125PEY1E8 U-140PEY1E8
Outdoor power source V 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 25,00 30,00 16,00 16,00 16,00
Current in cooling (1p 230V / 3p 400) A 4,00 6,00 2,50 2,50 2,50
Current in cooling (1p 240V / 3p 415) A 8,40 12,20 15,10 18,80 5,10 6,20 6,75
Current in heating (1p 220V / 3p 380) A 8,10 11,70 14,50 18,00 4,85 5,90 6,45
Current in heating (1p 230V / 3p 400) A 7,75 11,20 13,90 17,20 4,70 5,70 6,25
Current in heating (1p 240V / 3p 415) A 6,30 8,15 11,80 14,60 4,05 4,90 5,60
Outdoor air flow (Cool) m³/min 6,05 7,80 11,20 14,00 3,80 4,65 5,40
Outdoor air flow (Heat) m³/min 5,80 7,45 10,70 13,40 3,65 4,50 5,20
Outdoor sound pressure (Cool -Hi) dB(A) 38 44 76 80 76 80 135
Outdoor sound pressure (Heat -Hi) dB(A) 41 41 67 73 67 73 120
Outdoor sound power (Cool -Hi) dB(A) 46 49 54 56 54 56 54
Outdoor sound power (Heat -Hi) dB(A) 48 49 54 56 54 56 53
Outdoor dimension (Height) mm 619 619 996 996 996 996 1416
Outdoor dimension (Width) mm 799 799 940 940 940 940 940
Outdoor dimension (Depth) mm 299 299 340 340 340 340 340
Outdoor net weight kg 40 40 73 85 73 85 98
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
Pipe length range m 3 ~ 40 3 ~ 40 5 ~ 50 5 ~ 50 5 ~ 50 5 ~ 50 5 ~ 50
Elevation difference (in/out) (7) m 30 30 30 30 30 30 30
Pipe length for additional gas m 30 30 30 30 30 30 30
Additional gas amount g/m 40 40 50 50 50 50 50
Refrigerant (R410A) / CO2 Eq. kg / T 1,95 / 4,0716 1,95 / 4,0716 2,60 / 5,4288 3,20 / 6,6816 2,60 / 5,4288 3,20 / 6,6816 3,40 / 7,0992
Operating range (Cool - Min) °C -10 -10 -10 -10 -10 -10 -10
Operating range (Cool - Max) °C +43 +43 +43 +43 +43 +43 +43
Operating range (Heat - Min) °C -15 -15 -15 -15 -15 -15 -15
Operating range (Heat - Max) °C +24 +24 +24 +24 +24 +24 +24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Heating capacity is calculated including defrost factor correction.
(5) Medium external static pressure setting from factory.
(6) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(7) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.

Accessoires