Bi-bloc M Series 1 phase – 3 phase · R290
12.00kW
WH-WDG12ME8 + WH-SDC0316M9E8
Aquarea High Performance M Series, the next generation of heat pumps with R290
Specifications
| Bi-bloc M Series 1 phase – 3 phase · R290 | |||
|---|---|---|---|
| 12.00 kW | |||
| Outdoor unit | WH-WDG12ME8 | ||
| Heating capacity (A +7°C, W 35°C) | kW | 12,00 | |
| COP (A +7°C, W 35°C) | 4,88 | ||
| Heating capacity (A +7°C, W 55°C) | kW | 12,00 | |
| COP (A +7°C, W 55°C) | 3,06 | ||
| Heating capacity (A +2°C, W 35°C) | kW | 12,00 | |
| COP (A +2°C, W 35°C) | 3,46 | ||
| Heating capacity (A +2°C, W 55°C) | kW | 12,00 | |
| COP (A +2°C, W 55°C) | 2,27 | ||
| Heating capacity (A -7°C, W 35°C) | kW | 10,50 | |
| COP (A -7°C, W 35°C) | 3,00 | ||
| Heating capacity (A -7°C, W 55°C) | kW | 10,00 | |
| COP (A -7°C, W 55°C) | 1,97 | ||
| Cooling capacity (A 35°C, W 7°C) | kW | 9,00 | |
| EER (A 35°C, W 7°C) | 3,61 | ||
| Cooling capacity (A 35°C, W 18°C) | kW | 9,00 | |
| EER (A 35°C, W 18°C) | 5,26 | ||
| Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 4,65 / 3,58 | |
| Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 183 / 140 | |
| Heating average climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A++ | |
| Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 6,20 / 4,34 | |
| Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 245 / 171 | |
| Heating warm climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A+++ | |
| Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 4,35 / 3,26 | |
| Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 171 / 127 | |
| Heating cold climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A++ / A++ | |
| Outdoor sound power (Heat) (2) | dB(A) | 55 | |
| Outdoor dimension (Height) | mm | 1.520 | |
| Outdoor dimension (Width) | mm | 1.200 | |
| Outdoor dimension (Depth) | mm | 370 | |
| Outdoor net weight | kg | 151 | |
| A class pump (Number of speeds) | Variable speed | ||
| A class pump (Input power Min) | W | 30 | |
| A class pump (Input power Max) | W | 175 | |
| Heating water flow (∆T=5 K. 35°C) | L/min | 34,4 | |
| Refrigerant (R290) / CO2 Eq. (3) | kg / T | 1,58 / 0,00003 | |
| Operation range - Outdoor ambient (Heat) | °C | -25 ~ +35 | |
| Operation range - Outdoor ambient (Cool) | °C | +10 ~ +43 | |
| Water outlet (Cool) | °C | 5 ~ 20 | |
| Indoor unit 3kW electric heater | — | ||
| Indoor unit 6kW electric heater | — | ||
| Indoor unit 9kW electric heater | WH-SDC0316M9E8 | ||
| Indoor dimension (Height) | mm | 892 | |
| Indoor dimension (Width) | mm | 500 | |
| Indoor dimension (Depth) | mm | 348 | |
| Indoor net weight | kg | 29 | |
| Water pipe connector (room) | Inch | 1¼ | |
| Water pipe connector (indoor units) | Inch | 1¼ | |
| Water pipe connector (outdoor units) | Inch | 1¼ | |
| Pipe length range standard | m | 5 | |
| Pipe length range maximum | m | 30 | |
| Elevation difference (in/out) | m | 30 | |
(1) Scale from A+++ to D.
(2) Sound power level in accordance with EN 12102 under conditions of the EN 14825 (part load).
(3) WH-WDG models are hermetically sealed.
(4) Water outlet up to 75°C above -15°C outdoor. Between outdoor ambient -15°C and -25°C, the water outlet temperature gradually decreases from 75°C to 55°C.
(5) Check local regulations.
*EER and COP calculation is based in accordance with EN 14511.
**This product is designed to comply with the European drinking water standard (EU) 2020/2184. The lifespan of the product is not guaranteed in the case of the use of groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to these cases are the customer’s responsibility.