Pompe di calore aria - acqua
Riscaldamento, raffrescamento e acqua calda sanitaria
per un futuro sostenibile
Aquarea High Performance Mono-bloc H Generation 1 Phase • R410A | Monofase | ||||||
---|---|---|---|---|---|---|---|
5 kW | 7 kW | 9 kW | 12 kW | 16 kW | |||
Outdoor unit | WH-MDC05H3E5 | WH-MDC07H3E5 | WH-MDC09H3E5 | WH-MDC12H6E5 | WH-MDC16H6E5 | ||
Heating capacity (A +7°C, W 35°C) | kW | 5,00 | 7,00 | 9,00 | 12,00 | 16,00 | |
COP (A +7°C, W 35°C) | 5,08 | 4,52 | 4,29 | 4,74 | 4,28 | ||
Heating capacity (A +7°C, W 55°C) | kW | 5,00 | 7,00 | 9,00 | 12,00 | 14,50 | |
COP (A +7°C, W 55°C) | 2,84 | 2,83 | 2,72 | 2,93 | 2,72 | ||
Heating capacity (A +2°C, W 35°C) | kW | 4,80 | 6,60 | 6,80 | 11,40 | 13,00 | |
COP (A +2°C, W 35°C) | 3,36 | 3,30 | 3,18 | 3,44 | 3,28 | ||
Heating capacity (A +2°C, W 55°C) | kW | 4,00 | 6,30 | 6,30 | 9,10 | 9,80 | |
COP (A +2°C, W 55°C) | 2,33 | 2,22 | 2,13 | 2,23 | 2,21 | ||
Heating capacity (A -7°C, W 35°C) | kW | 4,70 | 5,50 | 6,40 | 10,00 | 11,40 | |
COP (A -7°C, W 35°C) | 2,85 | 2,70 | 2,60 | 2,73 | 2,57 | ||
Heating capacity (A -7°C, W 55°C) | kW | 4,30 | 5,00 | 5,80 | 8,20 | 9,00 | |
COP (A -7°C, W 55°C) | 1,89 | 1,82 | 1,78 | 1,95 | 1,84 | ||
Cooling capacity (A 35°C, W 7°C) | kW | 4,50 | 6,00 | 7,00 | 10,00 | 12,20 | |
EER (A 35°C, W 7°C) | 3,28 | 2,78 | 2,60 | 2,81 | 2,56 | ||
Cooling capacity (A 35°C, W 18°C) | kW | 5,10 | 6,00 | 7,00 | 10,00 | 12,20 | |
EER (A 35°C, W 18°C) | 5,10 | 3,87 | 3,59 | 4,65 | 4,12 | ||
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 199 / 139 | 190 / 130 | 190 / 130 | 190 / 134 | 190 / 130 | |
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 5,05 / 3,55 | 4,83 / 3,33 | 4,83 / 3,33 | 4,83 / 3,43 | 4,83 / 3,33 | |
Heating average climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A++ | A+++ / A++ | A+++ / A++ | A+++ / A++ | A+++ / A++ | |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 237 / 161 | 225 / 160 | 225 / 160 | 245 / 159 | 245 / 169 | |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 6,00 / 4,10 | 5,70 / 4,08 | 5,70 / 4,08 | 6,20 / 4,05 | 6,20 / 4,30 | |
Heating warm climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | A+++ / A+++ | |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 160 / 115 | 160 / 115 | 160 / 115 | 168 / 121 | 168 / 121 | |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 4,08 / 2,95 | 4,08 / 2,95 | 4,08 / 2,95 | 4,28 / 3,10 | 4,28 / 3,10 | |
Heating cold climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A++ / A+ | A++ / A+ | A++ / A+ | A++ / A+ | A++ / A+ | |
Outdoor sound power part load (Heat) (1) | dB(A) | 55 | 59 | 59 | 65 | 65 | |
Outdoor sound power full load (Heat) | dB(A) | 65 | 68 | 69 | 69 | 72 | |
Outdoor sound power full load (Cool) | dB(A) | 65 | 66 | 67 | 68 | 72 | |
Outdoor dimension (Height) | mm | 865 | 865 | 865 | 1410 | 1410 | |
Outdoor dimension (Width) | mm | 1283 | 1283 | 1283 | 1283 | 1283 | |
Outdoor dimension (Depth) | mm | 320 | 320 | 320 | 320 | 320 | |
Outdoor net weight | kg | 94 | 104 | 104 | 140 | 140 | |
Refrigerant (R32) / CO2 Eq. (2) | kg / T | 1,30 / 2714 | 1,35 / 2819 | 1,35 / 2819 | 2,10 / 4,385 | 2,10 / 4,385 | |
Refrigerant (R410A) / CO2 Eq. (2) | kg / T | 1,30 / 2714 | 1,35 / 2819 | 1,35 / 2819 | 2,10 / 4,385 | 2,10 / 4,385 | |
Water pipe connector | Inch | R 1¼ | R 1¼ | R 1¼ | R 1¼ | R 1¼ | |
Pump (Number of speeds) | Variable Speed | Variable Speed | Variable Speed | Variable Speed | Variable Speed | ||
Pump (Input power Min) | W | 34 | 36 | 39 | 34 | 38 | |
Pump (Input power Max) | W | 96 | 100 | 108 | 110 | 120 | |
Heating water flow (∆T=5 K. 35°C) | L/min | 14,30 | 20,10 | 25,80 | 34,40 | 45,90 | |
Capacity of integrated electric heater | kW | 3,00 | 3,00 | 3,00 | 6,00 | 6,00 | |
Input power (Heat) | kW | 0,99 | 1,55 | 2,10 | 2,53 | 3,74 | |
Input power (Cool) | kW | 1,37 | 2,16 | 2,69 | 3,56 | 4,76 | |
Running and starting current (Heat) | A | 4,7 | 7,2 | 9,6 | 11,7 | 16,9 | |
Running and starting current (Cool) | A | 6,3 | 9,9 | 12,2 | 16,2 | 21,5 | |
Current 1 | A | 13 | 21 | 22,9 | 24 | 26 | |
Current 2 | A | 13 | 13 | 13 | 26 | 26 | |
Indoor recommended fuse | A | 30 / 15 | 30 / 15 | 30 / 16 | 30 / 30 | 30 / 30 | |
Recommended cable size, supply 1 | mm² | 3 x 4,0 or 6,0 | 3 x 4,0 or 6,0 | 3 x 4,0 or 6,0 | 3 x 4,0 or 6,0 | 3 x 4,0 or 6,0 | |
Recommended cable size, supply 2 | mm² | 3 x 4,0 | 3 x 4,0 | 3 x 4,0 | 3 x 4,0 | 3 x 4,0 | |
Operation range - outdoor temperature (Heat) | °C | -20 ~ +35 | -20 ~ +35 | -20 ~ +35 | -20 ~ +35 | -20 ~ +35 | |
Water outlet (Heat) | °C | 20 ~ 55 | 20 ~ 55 | 20 ~ 55 | 25 ~ 55 | 25 ~ 55 | |
Water outlet (Cool) | °C | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 | 5 ~ 20 |
(1) Sound power in accordance to 8112013,81312013 and EN12102-1:2017 at +7°C.
(2) WH-MDC models are hermetically sealed.
EER and COP calculation is based in accordance to EN14511.