Aquarea T-CAP Bi-bloc H Generation 3 Phase. Super Quiet outdoor unit • R410A THREE PHASE (Power to indoor)
9 kW 12 kW 16 kW
Kit KIT-WQC09H3E8 KIT-WQC12H9E8 KIT-WQC16H9E8
Heating capacity (A +7°C, W 35°C) kW 9,00 12,00 16,00
COP (A +7°C, W 35°C) 4,84 4,74 4,28
Heating capacity (A +7°C, W 55°C) kW 9,00 12,00 16,00
COP (A +7°C, W 55°C) 2,94 2,88 2,71
Heating capacity (A +2°C, W 35°C) kW 9,00 12,00 16,00
COP (A +2°C, W 35°C) 3,59 3,44 3,10
Heating capacity (A +2°C, W 55°C) kW 9,00 12,00 16,00
COP (A +2°C, W 55°C) 2,21 2,19 2,13
Heating capacity (A -7°C, W 35°C) kW 9,00 12,00 16,00
COP (A -7°C, W 35°C) 2,85 2,72 2,49
Heating capacity (A -7°C, W 55°C) kW 9,00 12,00 16,00
COP (A -7°C, W 55°C) 2,02 1,92 1,86
Cooling capacity (A 35°C, W 7°C) kW 7,00 10,00 12,20
EER (A 35°C, W 7°C) 3,17 2,81 2,57
Cooling capacity (A 35°C, W 18°C) kW 7,00 10,00 12,20
EER (A 35°C, W 18°C) 5,19 5,13 3,49
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 181 / 130 170 / 130 160 / 125
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,60 / 3,33 4,33 / 3,33 4,08 / 3,20
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A++ A++ / A++ A++ / A++
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 235 / 158 231 / 158 231 / 159
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 5,95 / 4,03 5,85 / 4,03 5,85 / 4,05
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++ A+++ / A+++ A+++ / A+++
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 160 / 125 160 / 125 150 / 125
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,08 / 3,20 4,08 / 3,20 3,83 / 3,20
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A++ / A++ A++ / A++ A++ / A++
Indoor unit WH-SQC09H3E8 WH-SQC12H9E8 WH-SQC16H9E8
Indoor sound pressure (Heat) dB(A) 33 33 33
Indoor sound pressure (Cool) dB(A) 33 33 33
Indoor dimension (Height) mm 892 892 892
Indoor dimension (Width) mm 500 500 500
Indoor dimension (Depth) mm 340 340 340
Indoor net weight kg 43 44 45
Water pipe connector Inch R 1¼ R 1¼ R 1¼
A class pump (Number of speeds) Variable Speed Variable Speed Variable Speed
A class pump (Input power Min) W 32 34 30
A class pump (Input power Max) W 102 110 105
Heating water flow (∆T=5 K. 35°C) L/min 25,80 34,40 45,90
Capacity of integrated electric heater kW 3,00 9,00 9,00
Indoor recommended fuse A 15 / 30 15 / 30 15 / 30
Recommended cable size, supply 1 mm² 5 x 1,5 5 x 1,5 5 x 1,5
Recommended cable size, supply 2 mm² 3 x 1,5 5 x 1,5 5 x 1,5
Outdoor unit WH-UQ09HE8 WH-UQ12HE8 WH-UQ16HE8
Outdoor sound power part load (Heat) (3) dB(A) 58 58 62
Outdoor sound power full load (Heat) dB(A) 61 62 65
Outdoor sound power full load (Cool) dB(A) 63 64 68
Outdoor dimension (Height) mm 1410 1410 1410
Outdoor dimension (Width) mm 1283 1283 1283
Outdoor dimension (Depth) mm 320 320 320
Outdoor net weight kg 151 151 161
Refrigerant (R410A) / CO2 Eq. kg / T 2,85 / 5,951 2,85 / 5,951 2,99 / 6,243
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
Pipe length range m 3 ~ 30 3 ~ 30 3 ~ 30
Elevation difference (in/out) m 20 20 20
Pipe length for additional gas m 10 10 10
Additional gas amount g/m 50 50 50
Operation range (Outdoor ambient) °C -28 ~ +35 -28 ~ +35 -28 ~ +35
Water outlet (Heat) °C 20 ~ 60 20 ~ 60 20 ~ 60
Water outlet (Cool) °C 5 ~ 20 5 ~ 20 5 ~ 20

(1) Sound power in accordance to 8112013,81312013 and EN12102-1:2017 at +7°C.