Low Static Pressure Hide Away Inverter • R32
3.5kW
KIT-Z35-UD3 (CS-Z35UD3EAW + CU-Z35UBEA)
Low static pressure hide away with compact indoor unit only 200m high
The duct can also be connected to KNX, Modbus interfaces for easy integration with your BMS systems. This interfaces have dry contacts (ON/OFF, error message) for easy integration.
- Duct type can be controlled by KNX and Modbus
- Eco mode for 20 % energy saving
- Extremely compact indoor units without losing static pressure (only 200 mm high)
- Weekly timer, 42 settings per week
- Easy check mode for failure detection
- Drain pump included
Descoperiți ultima generație de sisteme de aer condiționat
Economii remarcabile și stare de bine sporită
Aparatele noastre de aer condiționat asigură un confort excelent cu un cost foarte mic în ceea ce privește consumul de energie, un aer sănătos fără viruși, bacterii, polen și mirosuri.
O gamă de produse special concepute pentru dumneavoastră
De la soluțiile mai mici 1x1 la cele complete 5x1, nevoile dumneavoastră contează. Panasonic poate să vă ofere cea mai bună soluție pentru a obține cel mai bun climat în locuința dumneavoastră.
Confort în casă pe toată durata anului
Aparatele noastre de aer condiționat vă oferă cea mai confortabilă temperatură pe toată durata anului, încălzire pe timp de iarnă, răcire pe timp de vară și o curățare a atmosferei pe toată durata anului.
Economii remarcabile și stare de bine sporită
Aparatele noastre de aer condiționat asigură un confort excelent cu un cost foarte mic în ceea ce privește consumul de energie, un aer sănătos fără viruși, bacterii, polen și mirosuri.
O gamă de produse special concepute pentru dumneavoastră
De la soluțiile mai mici 1x1 la cele complete 5x1, nevoile dumneavoastră contează. Panasonic poate să vă ofere cea mai bună soluție pentru a obține cel mai bun climat în locuința dumneavoastră.
Confort în casă pe toată durata anului
Aparatele noastre de aer condiționat vă oferă cea mai confortabilă temperatură pe toată durata anului, încălzire pe timp de iarnă, răcire pe timp de vară și o curățare a atmosferei pe toată durata anului.
Gestionați soluțiile Panasonic oricând, oriunde
Specificații
| Low Static Pressure Hide Away Inverter • R32 | |||
|---|---|---|---|
| 3.5 kW | |||
| Cooling capacity (Min) | kW | 0,85 | |
| Input power heating (Min) | kW | 0,23 | |
| COP (Max) (1) | W/W | 3,59 | |
| COP (Min) (1) | W/W | 3,70 | |
| Heating capacity (Max) | kW | 5,10 | |
| Heating capacity (Min) | kW | 0,85 | |
| Input power cooling (Max) | kW | 1,19 | |
| Input power cooling (Min) | kW | 0,24 | |
| EER (Max) (1) | W/W | 3,36 | |
| EER (Min) (1) | W/W | 3,54 | |
| Cooling capacity (Max) | kW | 4,00 | |
| Input power heating (Max) | kW | 1,42 | |
| Operating range (Heat - Max) | °C | +24 | |
| Operating range (Heat - Min) | °C | -15 | |
| Operating range (Cool - Max) | °C | +43 | |
| Elevation difference (in/out) (6) | m | 15 | |
| Outdoor dimension (Depth) (5) | mm | 299 | |
| Outdoor dimension (Width) (5) | mm | 824 | |
| Outdoor dimension (Height) (5) | mm | 619 | |
| Outdoor sound pressure (Heat -Hi) (4) | dB(A) | 48 | |
| Outdoor unit | CU-Z35UBEA | ||
| Outdoor connection indoor / outdoor | mm² | 4 x 1,5 ~ 2,5 | |
| Outdoor recommended fuse | A | 16 | |
| External static pressure (Max) (7) | Pa | 45 | |
| Outdoor air flow (Heat) | m³/min | 33,5 | |
| Outdoor air flow (Cool) | m³/min | 34,3 | |
| Indoor unit | CS-Z35UD3EAW | ||
| Indoor sound pressure (Heat -Q-Lo) (4) | dB(A) | 24 | |
| Indoor sound pressure (Heat -Lo) (4) | dB(A) | 27 | |
| Indoor sound pressure (Heat -Hi) (4) | dB(A) | 35 | |
| Indoor sound pressure (Cool -Q-Lo) (4) | dB(A) | 24 | |
| Indoor sound pressure (Cool -Lo) (4) | dB(A) | 27 | |
| Moisture removal volume | L/h | 2,0 | |
| Indoor air flow (Heat) | m³/min | 11,2 | |
| Indoor air flow (Cool) | m³/min | 11,2 | |
| Indoor sound pressure (Cool -Hi) (4) | dB(A) | 33 | |
| SCOP (2) | 4,10 A+ | ||
| Annual energy consumption heating (3) | kWh/a | 956 | |
| Annual energy consumption cooling (3) | kWh/a | 211,00 | |
| Input power cooling (Nominal) | kW | 0,91 | |
| Pdesign (cooling) | kW | 3,50 | |
| SEER (2) | 5,80 A+ | ||
| Outdoor net weight | kg | 35 | |
| Outdoor sound pressure (Cool -Hi) (4) | dB(A) | 48 | |
| Indoor net weight | kg | 19 | |
| Indoor dimension (Height) | mm | 200 | |
| Pdesign at -10°C | kW | 2,80 | |
| Indoor power source | V | 230 | |
| Pipe length range | m | 3 ~ 20 | |
| Refrigerant (R32) / CO2 Eq. | kg / T | 0,93 / 0,628 | |
| Kit | KIT-Z35-UD3 | ||
| Additional gas amount | g/m | 10 | |
| Pipe length for additional gas | m | 7,5 | |
| Pipe diameter (Gas) | Inch (mm) | 3/8 (9,52) | |
| Pipe diameter (Liquid) | Inch (mm) | 1/4 (6,35) | |
| Indoor dimension (Depth) | mm | 640 | |
| Indoor dimension (Width) | mm | 750 | |
| Heating capacity at -7°C | kW | 3,00 | |
| EER (Nominal) (1) | W/W | 3,85 | |
| COP (Nominal) (1) | W/W | 3,82 | |
| External static pressure (Min) (7) | Pa | 15 | |
| Outdoor power source | V | 230 | |
| Heating capacity (Nominal) | kW | 4,20 | |
| Cooling capacity (Nominal) | kW | 3,50 | |
| Operating range (Cool - Min) | °C | -10 | |
| Input power heating (Nominal) | kW | 1,10 | |
(2) Energy Label Scale from A+++ to D.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the indoor unit shows the value measured of a position of 1,5m below the unit with 1m duct on the suction side and 2m duct on the discharge side. For outdoor unit 1m in front and 1m in rear side of main body. The sound pressure is measured in accordance with JIS C 9612.
(5) Add 100mm for indoor unit or 70mm for outdoor unit for piping port.
(6) When installing the outdoor unit at a higher position than the indoor unit.
(7) The specification listed on the table indicates values under the condition of 25Pa (2,5mmAq) which are applied for factory default setting. Change switch on PCB from Hi to S-Hi to have more than 6,0mmAq.