PACi NX Standard - Cassettes 4 voies 60x60 Inverter+ - R32
Cassette 4 voies 60x60 - PY3
De 2,5 à 6,0 kW (4 capacités)
Dimensions du châssis (H x L x P) : 243 x 575 x 575 mm
Pompe de vidange intégrée
Design compact et élégant.
La profondeur du plafonnier n’est que de 250 mm.
La zone exposée n’est que de 30 mm.
Contrôleur individuel de chaque volet.
Meilleur contrôle du débit d’air avec 4 moteurs.
La dernière génération de climatiseurs pour le tertiaire est arrivée
Caractéristiques
PACi NX Standard - Cassettes 4 voies 60x60 Inverter+ - R32 | |||
---|---|---|---|
5.0 kW | |||
Kit | KIT-50PY3Z5 | ||
Remote controller | CZ-RTC5B | ||
Cooling capacity (Nominal) | kW | 5,0 | |
Cooling capacity (Min) | kW | 1,5 | |
Cooling capacity (Max) | kW | 5,6 | |
EER (Nominal) (1) | W/W | 3,50 | |
EER (Min) (1) | W/W | 3,03 | |
EER (Max) (1) | W/W | 6,25 | |
SEER (2) | 7,3 A++ | ||
Pdesign (cooling) | kW | 5,0 | |
Input power cooling (Nominal) | kW | 1,43 | |
Annual energy consumption cooling (3) | kWh/a | 238 | |
Input power cooling (Min) | kW | 0,24 | |
Input power cooling (Max) | kW | 1,85 | |
Annual energy consumption cooling (3) | kWh/a | 238 | |
Heating capacity (Nominal) | kW | 5,0 | |
Heating capacity (Min) | kW | 1,5 | |
Heating capacity (Max) | kW | 6,4 | |
COP (Nominal) (1) | W/W | 3,94 | |
COP (Min) (1) | W/W | 2,91 | |
COP (Max) (1) | W/W | 7,50 | |
SCOP (2) | 4,4 A+ | ||
Pdesign at -10°C | kW | 4,0 | |
Input power heating (Nominal) | kW | 1,27 | |
Input power heating (Min) | kW | 0,20 | |
Input power heating (Max) | kW | 2,20 | |
Annual energy consumption heating (3) | kWh/a | 1.264 | |
Indoor unit | S-50PY3E | ||
Indoor air flow (Hi) | m³/min | 12,0 | |
Indoor air flow (Med) | m³/min | 9,5 | |
Indoor air flow (Lo) | m³/min | 6,5 | |
Moisture removal volume | L/h | 2,3 | |
Indoor sound pressure (Med) (4) | dB(A) | 34 | |
Indoor sound pressure (Lo) (4) | dB(A) | 27 | |
Indoor sound power (Hi) | dB(A) | 54 | |
Indoor sound power (Med) | dB(A) | 49 | |
Indoor sound power (Lo) | dB(A) | 42 | |
Indoor dimension (Height) | mm | 243 | |
Indoor dimension (Width) | mm | 575 | |
Indoor dimension (Depth) | mm | 575 | |
Panel dimension (Height) | mm | 30 | |
Panel dimension (Depth) | mm | 625 | |
Indoor net weight | kg | 15 | |
Panel net weight | kg | 2,8 | |
nanoe X Generator | Mark 2 | ||
Outdoor unit | U-50PZ3E5 | ||
Outdoor power source | V | 220 - 230 - 240 | |
Current in cooling (1p 220V / 3p 380) | A | 6,65 | |
Current in cooling (1p 230V / 3p 400) | A | 6,35 | |
Current in cooling (1p 240V / 3p 415) | A | 6,10 | |
Current in heating (1p 220V / 3p 380) | A | 5,695 | |
Current in heating (1p 230V / 3p 400) | A | 5,70 | |
Current in heating (1p 240V / 3p 415) | A | 5,45 | |
Outdoor air flow (Cool) | m³/min | 32,7 | |
Outdoor air flow (Heat) | m³/min | 31,9 | |
Outdoor sound pressure (Cool -Hi) | dB(A) | 46 | |
Outdoor sound pressure (Heat -Hi) | dB(A) | 48 | |
Outdoor sound power (Cool -Hi) | dB(A) | 64 | |
Outdoor sound power (Heat -Hi) | dB(A) | 64 | |
Outdoor dimension (Height) | mm | 619 | |
Outdoor dimension (Width) | mm | 824 | |
Outdoor dimension (Depth) | mm | 299 | |
Outdoor net weight | kg | 35 | |
Pipe diameter (Liquid) | Inch (mm) | 1/4 (6,35) | |
Pipe diameter (Gas) | Inch (mm) | 1/2 (12,70) | |
Pipe length range | m | 3 ~ 20 | |
Elevation difference (in/out) (5) | m | 15 / 15 | |
Pipe length for additional gas | m | 7,5 | |
Additional gas amount | g/m | 15 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 1,14 / 0,77 | |
Operating range (Cool - Min) | °C | -10 | |
Operating range (Cool - Max) | °C | +43 | |
Operating range (Heat - Min) | °C | -15 | |
Operating range (Heat - Max) | °C | +24 | |
Kit | KIT-50PY3Z5 | ||
Remote controller | CZ-RTC5B | ||
Cooling capacity (Nominal) | kW | 5,0 | |
Cooling capacity (Min) | kW | 1,5 | |
Cooling capacity (Max) | kW | 5,6 | |
EER (Nominal) (1) | W/W | 3,50 | |
EER (Min) (1) | W/W | 3,03 | |
EER (Max) (1) | W/W | 6,25 | |
SEER (2) | 7,3 A++ | ||
Pdesign (cooling) | kW | 5,0 | |
Input power cooling (Nominal) | kW | 1,43 | |
Input power cooling (Min) | kW | 0,24 | |
Input power cooling (Max) | kW | 1,85 | |
Annual energy consumption cooling (3) | kWh/a | 238 | |
Heating capacity (Nominal) | kW | 5,0 | |
Heating capacity (Min) | kW | 1,5 | |
Heating capacity (Max) | kW | 6,4 | |
COP (Nominal) (1) | W/W | 3,94 | |
COP (Min) (1) | W/W | 2,91 | |
COP (Max) (1) | W/W | 7,50 | |
SCOP (2) | 4,4 A+ | ||
Pdesign at -10°C | kW | 4,0 | |
Input power heating (Nominal) | kW | 1,27 | |
Input power heating (Min) | kW | 0,20 | |
Input power heating (Max) | kW | 2,20 | |
Annual energy consumption heating (3) | kWh/a | 1.264 | |
Indoor unit | S-50PY3E | ||
Indoor air flow (Hi) | m³/min | 12,0 | |
Indoor air flow (Med) | m³/min | 9,5 | |
Indoor air flow (Lo) | m³/min | 6,5 | |
Moisture removal volume | L/h | 2,3 | |
Indoor sound pressure (Med) (4) | dB(A) | 34 | |
Indoor sound pressure (Lo) (4) | dB(A) | 27 | |
Indoor sound power (Hi) | dB(A) | 54 | |
Indoor sound power (Med) | dB(A) | 49 | |
Indoor sound power (Lo) | dB(A) | 42 | |
Indoor dimension (Height) | mm | 243 | |
Indoor dimension (Width) | mm | 575 | |
Indoor dimension (Depth) | mm | 575 | |
Panel dimension (Height) | mm | 30 | |
Panel dimension (Depth) | mm | 625 | |
Indoor net weight | kg | 15 | |
Panel net weight | kg | 2,8 | |
nanoe X Generator | Mark 2 | ||
Outdoor unit | U-50PZ3E5 | ||
Outdoor power source | V | 220 - 230 - 240 | |
Current in cooling (1p 220V / 3p 380) | A | 6,65 | |
Current in cooling (1p 230V / 3p 400) | A | 6,35 | |
Current in cooling (1p 240V / 3p 415) | A | 6,10 | |
Current in heating (1p 220V / 3p 380) | A | 5,695 | |
Current in heating (1p 230V / 3p 400) | A | 5,70 | |
Current in heating (1p 240V / 3p 415) | A | 5,45 | |
Outdoor air flow (Cool) | m³/min | 32,7 | |
Outdoor air flow (Heat) | m³/min | 31,9 | |
Outdoor sound pressure (Cool -Hi) | dB(A) | 46 | |
Outdoor sound pressure (Heat -Hi) | dB(A) | 48 | |
Outdoor sound power (Cool -Hi) | dB(A) | 64 | |
Outdoor sound power (Heat -Hi) | dB(A) | 64 | |
Outdoor dimension (Height) | mm | 619 | |
Outdoor dimension (Width) | mm | 824 | |
Outdoor dimension (Depth) | mm | 299 | |
Outdoor net weight | kg | 35 | |
Pipe diameter (Liquid) | Inch (mm) | 1/4 (6,35) | |
Pipe diameter (Gas) | Inch (mm) | 1/2 (12,70) | |
Pipe length range | m | 3 ~ 20 | |
Elevation difference (in/out) (7) | m | 15 / 15 (8) | |
Pipe length for additional gas | m | 7,5 | |
Additional gas amount | g/m | 15 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 1,14 / 0,77 | |
Operating range (Cool - Min) | °C | -10 | |
Operating range (Cool - Max) | °C | +43 | |
Operating range (Heat - Min) | °C | -15 | |
Operating range (Heat - Max) | °C | +24 |
1) Le calcul des coefficients EER et COP est conforme à la norme européenne EN 14511.
2) Pour les modèles inférieurs à 12 kW, le valeurs SEER et SCOP sont calculées sur la base des valeurs définies dans le règlement délégué UE/626/2011. Pour les modèles de plus de 12 kW, les valeurs ηsc / ηsh respectent les valeurs définies par la directive EN 14825.
3) Réglage en usine.
4) Le niveau de pression sonore des unités indique la valeur mesurée pour une position à 1,5 m en dessous de l’unité. La pression sonore est mesurée conformément à la norme Eurovent 6/C/006-97.
5) Connectez le raccord de tube de liquide (Ø6,35-Ø9,52) au côté du tube de liquide de l’unité intérieure.
6) Connectez le raccord de tube de gaz (Ø12,70-Ø15,88) au côté du tube de gaz de l’unité intérieure.
7) Lors de l’installation de l’unité extérieure à une position plus élevée que l’unité intérieure.
8) Unité extérieure placée plus bas/unité extérieure placée plus haut.
* Fusible recommandé pour l’unité intérieure 3A.
** Les valeurs ci-dessous s’appliquent si nanoe™ X est désactivé.
*** Disponible à l’automne 2021.
**** Données provisoires.