7.1 kW. PACi Standard High Static Pressure Hide Away • R32

KIT-71PF1Z5 (S-71PF1E5B + U-71PZ2E5)

The ducted systems are the ideal solution for flexible, concealed air conditioning and the optional 200mm spigots ensure simple, hassle-free connection to spiral ductwork.

  • High ESP (external static pressure) up to 150 Pa
  • Automatic learning function for the required static pressure on site during commissioning (a standard wired remote controller is required)
  • DC FAN for better efficiency and control
  • Built in drain pump
  • Datanavi simple support tool App with remote controller (CZ-RTC5B)
  • Twin split options
  • Easy connection and control of external fan or ERV using the connector PAW-FDC on the indoor unit PCB. The external device can be controlled by the remote control of the Panasonic indoor unit

Specifications

See all
PACi Standard High Static Pressure Hide Away • R32 SINGLE PHASE
7.1 kW
Kit KIT-71PF1Z5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 7,1
Cooling capacity (Min) kW 2,0
Cooling capacity (Max) kW 7,7
EER (Nominal) (1) W/W 3,23
SEER (2) 6,1 A++
Pdesign (cooling) kW 7,1
Input power cooling (Nominal) kW 2,20
Annual energy consumption cooling (3) kWh/a 407
Heating capacity (Nominal) kW 7,1
Heating capacity (Min) kW 1,8
Heating capacity (Max) kW 8,1
COP (Nominal) (1) W/W 4,13
SCOP (2) 4,3 A+
Pdesign at -10°C kW 6,0
Input power heating (Nominal) kW 1,72
Annual energy consumption heating (3) kWh/a 1953
Indoor unit S-71PF1E5B
External static pressure (Nominal) (4) Pa 70
External static pressure (Min) (4) Pa 10
External static pressure (Max) (4) Pa 150
Indoor air flow (Hi) m³/min 21,0
Indoor air flow (Med) m³/min 19,0
Indoor air flow (Lo) m³/min 15,0
Moisture removal volume L/h 4,2
Indoor sound pressure (Hi) (5) dB(A) 35
Indoor sound pressure (Med) (5) dB(A) 32
Indoor sound pressure (Lo) (5) dB(A) 26
Indoor sound power (Hi) dB(A) 57
Indoor sound power (Med) dB(A) 54
Indoor sound power (Lo) dB(A) 48
Indoor dimension (Height) mm 290
Indoor dimension (Width) mm 1000
Indoor dimension (Depth) mm 700
Indoor net weight kg 33
Outdoor unit U-71PZ2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 10,40
Current in cooling (1p 230V / 3p 400) A 9,95
Current in cooling (1p 240V / 3p 415) A 9,50
Current in heating (1p 220V / 3p 380) A 8,10
Current in heating (1p 230V / 3p 400) A 7,75
Current in heating (1p 240V / 3p 415) A 7,40
Outdoor air flow (Cool) m³/min 50
Outdoor air flow (Heat) m³/min 45
Outdoor sound pressure (Cool -Hi) dB(A) 49
Outdoor sound pressure (Heat -Hi) dB(A) 49
Outdoor sound power (Cool -Hi) dB(A) 69
Outdoor sound power (Heat -Hi) dB(A) 69
Outdoor dimension (Height) mm 695
Outdoor dimension (Width) mm 875
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 44
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 3 ~ 40
Elevation difference (in/out) (6) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 35
Refrigerant (R32) / CO2 Eq. kg / T 1,45 / 0,979
Operating range (Cool - Min) °C -10
Operating range (Cool - Max) °C 43
Operating range (Heat - Min) °C -15
Operating range (Heat - Max) °C 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Medium External static pressure setting from factory.
(5) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(6) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.