iCOOL LCU Series – MT

Previous capacity Next capacity

5.1kW

LCU-KRC045M08

iCOOL LCU Series for MT applications

The variation of iCOOL to meet demanding installation environment requirements.

High performance inverter compressor base for commercial installations. Designed for MT applications. Equipped with hermetic scroll or rotary compressor. Perfect for low noise and city center applications.

To be installed with a remote, field-supplied condenser.

Specifications

See all
iCOOL LCU Series – MT
5.1 kW
Model LCU-KRC045M08
Compressors Single compressor
Compatible refrigerants R448A, R449A, R134a, R513A
PED CAT I
Application and nominal cooling capacity MT/LT (kW) MT (5,1)
MT (R449A/R448A) - Cooling capacity at .
ET -15°C, CT 40°C (Min - Max) kW 0,6 - 4,5
ET -15°C, CT 45°C (Min - Max) kW 0,5 - 4,2
ET -15°C, CT 50°C (Min - Max) kW 0,5 - 3,9
ET -10°C, CT 40°C (Min - Max) kW 0,7 - 5,4
ET -10°C, CT 45°C (Min - Max) kW 0,7 - 5,1
ET -10°C, CT 50°C (Min - Max) kW 0,6 - 4,7
ET -5°C, CT 40°C (Min - Max) kW 0,9 - 6,5
ET -5°C, CT 45°C (Min - Max) kW 0,8 - 6,1
ET -5°C, CT 50°C (Min - Max) kW 0,7 - 5,7
MT (R134a/R513A) - Cooling capacity at .
ET -15°C; CT 40°C (Min - Max) kW 0,4 - 2,4
ET -15°C; CT 45°C (Min - Max) kW 0,4 - 2,3
ET -15°C; CT 50°C (Min - Max) kW 0,5 - 3,9
ET -10°C; CT 45°C (Min - Max) kW 0,5 - 2,8
ET -10°C; CT 50°C (Min - Max) kW 0,4 - 2,6
ET -5°C; CT 40°C (Min - Max) kW 0,9 - 6,5
ET -5°C; CT 45°C (Min - Max) kW 0,8 - 6,1
ET -5°C; CT 50°C (Min - Max) kW 0,7 - 5,7
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 4,9
Maximum operating current (in the most loaded phase at 400V 50Hz) A 7,5
Maximum power consumption kW 3,5
Dimension (Width) mm 1.000
Dimension (Height) mm 705
Dimension (Depth) mm 530
Net weight kg 85
Sound level at 10m dB(A) 39,0
Oil charge dm³ 0,7 + 0,4
Connections (Suction) Inch (mm) 5/8
Connections (Liquid) Inch (mm) 3/8
Liquid receiver dm³ 3,9
Length of connection piping m 40
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 13
Maximum quantity of evaporators connected Qty. 5
Evaporation temperature (Min) °C -15
Evaporation temperature (Max) °C 5
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Compressor - additional data .
Compressor model C-7RVN113L0A
Volumetric flow m³/h 1,25 - 7,5
Rotation range rps 15-90
Current (Full load amperage) A 5,8
Current (Peak current limit / Locked rotor amperage) A 11,2 / —
Oil type FV68S (PVE)
Crankcase heater power consumption W 35
CU power supply .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x2,5
Recommended minimum protection C16

* ET: Evaporation Temperature. CT: Condensing Temperature.

Complementary products