19.6kW

LCU-KSC190M08

iCOOL LCU Series for MT applications

The variation of iCOOL to meet demanding installation environment requirements.

High performance inverter compressor base for commercial installations. Designed for MT applications. Equipped with hermetic scroll or rotary compressor. Perfect for low noise and city center applications.

To be installed with a remote, field-supplied condenser.

Specifications

See all
iCOOL LCU Series – MT
19.6 kW
Model LCU-KSC190M08
Compressors Tandem compressor
Compatible refrigerants R448A, R449A, R134a, R513A
PED CAT II
Application and nominal cooling capacity MT/LT (kW) MT (19,6)
MT (R449A/R448A) - Cooling capacity at .
ET -15°C, CT 40°C (Min - Max) kW 1,9 - 17,0
ET -15°C, CT 45°C (Min - Max) kW 1,4 - 15,1
ET -15°C, CT 50°C (Min - Max) kW 0,8 - 13,3
ET -10°C, CT 40°C (Min - Max) kW 2,8 - 21,8
ET -10°C, CT 45°C (Min - Max) kW 2,3 - 19,6
ET -10°C, CT 50°C (Min - Max) kW 1,9 - 17,7
ET -5°C, CT 40°C (Min - Max) kW 3,8 - 27,4
ET -5°C, CT 45°C (Min - Max) kW 3,3 - 25,0
ET -5°C, CT 50°C (Min - Max) kW 2,9 - 22,8
MT (R134a/R513A) - Cooling capacity at .
ET -15°C; CT 40°C (Min - Max) kW 1,8 - 10,9
ET -15°C; CT 45°C (Min - Max) kW 1,6 - 10,1
ET -15°C; CT 50°C (Min - Max) kW 0,8 - 13,3
ET -10°C; CT 45°C (Min - Max) kW 2,0 - 12,4
ET -10°C; CT 50°C (Min - Max) kW 1,9 - 11,6
ET -5°C; CT 40°C (Min - Max) kW 3,8 - 27,4
ET -5°C; CT 45°C (Min - Max) kW 3,3 - 25,0
ET -5°C; CT 50°C (Min - Max) kW 2,9 - 22,8
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 24,5
Maximum operating current (in the most loaded phase at 400V 50Hz) A 30,3
Maximum power consumption kW 16,7
Dimension (Width) mm 1.300
Dimension (Height) mm 874
Dimension (Depth) mm 662
Net weight kg 211
Sound level at 10m dB(A) 54,0
Oil charge dm³ 2,0 + 1,7 + 2x0,4
Connections (Suction) Inch (mm) 1 1/8
Connections (Liquid) Inch (mm) 5/8
Liquid receiver dm³ 14
Length of connection piping m 50
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 13
Maximum quantity of evaporators connected Qty. 10
Evaporation temperature (Min) °C -15
Evaporation temperature (Max) °C 10
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Compressor - additional data .
Compressor model C-SBS180H00B/ C-SBN453H8G
Volumetric flow m³/h 5,8 - 17,4 / 14,7
Rotation range rps 32-90
Current (Full load amperage) A 15,2 / 11,9
Current (Peak current limit / Locked rotor amperage) A 34 / 66
Oil type FV68S (PVE)
Crankcase heater power consumption W 2x70
CU power supply .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x10,0
Recommended minimum protection C40

* ET: Evaporation Temperature. CT: Condensing Temperature.