iCOOL LCU Series – MT

38.0kW

LCU-KSC400M08

iCOOL LCU Series for MT applications

The variation of iCOOL to meet demanding installation environment requirements.

High performance inverter compressor base for commercial installations. Designed for MT applications. Equipped with hermetic scroll or rotary compressor. Perfect for low noise and city center applications.

To be installed with a remote, field-supplied condenser.

Specifications

See all
iCOOL LCU Series – MT
38.0 kW
Model LCU-KSC400M08
Compressors Tandem compressor
Compatible refrigerants R448A, R449A, R134a, R513A
PED CAT II
Application and nominal cooling capacity MT/LT (kW) MT (38,0)
MT (R449A/R448A) - Cooling capacity at .
ET -15°C, CT 40°C (Min - Max) kW 4,7 - 33,3
ET -15°C, CT 45°C (Min - Max) kW 4,4 - 30,9
ET -15°C, CT 50°C (Min - Max) kW 3,8 - 28,7
ET -10°C, CT 40°C (Min - Max) kW 5,1 - 41,0
ET -10°C, CT 45°C (Min - Max) kW 5,4 - 38,0
ET -10°C, CT 50°C (Min - Max) kW 4,9 - 35,2
ET -5°C, CT 40°C (Min - Max) kW 7,4 - 50,7
ET -5°C, CT 45°C (Min - Max) kW 6,7 - 46,8
ET -5°C, CT 50°C (Min - Max) kW 6,1 - 43,2
MT (R134a/R513A) - Cooling capacity at .
ET -15°C; CT 40°C (Min - Max) kW 2,9 - 23,5
ET -15°C; CT 45°C (Min - Max) kW 2,7 - 21,7
ET -15°C; CT 50°C (Min - Max) kW 3,8 - 28,7
ET -10°C; CT 45°C (Min - Max) kW 3,4 - 26,7
ET -10°C; CT 50°C (Min - Max) kW 3,1 - 24,5
ET -5°C; CT 40°C (Min - Max) kW 7,4 - 50,7
ET -5°C; CT 45°C (Min - Max) kW 6,7 - 46,8
ET -5°C; CT 50°C (Min - Max) kW 6,1 - 43,2
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 36,9
Maximum operating current (in the most loaded phase at 400V 50Hz) A 51
Maximum power consumption kW 26,6
Dimension (Width) mm 1.860
Dimension (Height) mm 975
Dimension (Depth) mm 890
Net weight kg 380
Sound level at 10m dB(A) 55,0
Oil charge dm³ 2x2,8 + 2,0
Connections (Suction) Inch (mm) 1 5/8
Connections (Liquid) Inch (mm) 7/8
Liquid receiver dm³ 30
Length of connection piping m 70
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 13
Maximum quantity of evaporators connected Qty. 20
Evaporation temperature (Min) °C -15
Evaporation temperature (Max) °C 10
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Compressor - additional data .
Compressor model 4CC149NA04/ C-SCN753H8T
Volumetric flow m³/h 10,7 - 39,3/30,3
Rotation range rps 21-75
Current (Full load amperage) A 26,0 / 19,4
Current (Peak current limit / Locked rotor amperage) A 52 / 96
Oil type FV68S (PVE)
Crankcase heater power consumption W 2x90
CU power supply .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x16,0
Recommended minimum protection C63

* ET: Evaporation Temperature. CT: Condensing Temperature.