iCOOL SCU Series – MT

Previous capacity Next capacity

16.00kW

SCU-KSC160M08

iCOOL SCU Series for MT applications

Models with high pressure fan for indoor mounting.

A Plug & Play HFO/HFC solution designed specifically for indoor installations.
This compact unit helps minimize installation time and reduce overall costs compared to central systems with remote condensers.

Specifications

See all
iCOOL SCU Series – MT
16.00 kW
Model SCU-KSC160M08
Compressors Tandem compressor
Compatible refrigerants R448A, R449A, R134a, R513A
PED CAT II
Application and nominal cooling capacity MT/LT (kW) MT (16,0)
MT (R449A/R448A) - Cooling capacity at .
ET -15°C, AT 32°C (Min - Max) kW 2,3 - 13,2
ET -15°C, AT 38°C (Min - Max) kW 2,1 - 11,8
ET -15°C, AT 43°C (Min - Max) kW 1,9 - 10,7
ET -10°C, AT 32°C (Min - Max) kW 2,9 - 16,3
ET -10°C, AT 38°C (Min - Max) kW 2,6 - 14,6
ET -10°C, AT 43°C (Min - Max) kW 2,4 - 13,3
ET -5°C, AT 32°C (Min - Max) kW 3,6 - 19,8
ET -5°C, AT 38°C (Min - Max) kW 3,2 - 17,9
ET -5°C, AT 43°C (Min - Max) kW 3,0 - 16,4
MT (R134a/R513A) - Cooling capacity at .
ET -15°C; AT 32°C (Min - Max) kW 1,7 - 8,9
ET -15°C; AT 38°C (Min - Max) kW 1,6 - 8,2
ET -15°C; AT 43°C (Min - Max) kW — - —
ET -10°C; AT 32°C (Min - Max) kW 2,2 - 10,8
ET -10°C; AT 38°C (Min - Max) kW 2,0 - 10,0
ET -10°C; AT 43°C (Min - Max) kW 1,9 - 9,4
ET -5°C; AT 32°C (Min - Max) kW 2,8 - 13,1
ET -5°C; AT 38°C (Min - Max) kW 2,6 - 12,2
ET -5°C; AT 43°C (Min - Max) kW 2,4 - 11,4
SEPR cooling at ET -10°C AT 32°C 3,14
SEPR freezing at ET -35°C AT 32°C
Annual electricity consumption at ET -10°C AT 32°C kWh/a 31.411
Annual electricity consumption at ET -35°C AT 32°C kWh/a
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 23,6
Maximum operating current (in the most loaded phase at 230 - 400V 50Hz) A 30,5
Maximum power consumption kW 14,6
Dimension (Width) mm 1.327
Dimension (Height) mm 1.558
Dimension (Depth) mm 745
Net weight kg 342
Sound level at 10m dB(A) 55,0
Oil charge dm³ 2,0 + 1,7 + 2x0,4
Connections (Suction) Inch (mm) 1 1/8
Connections (Liquid) Inch (mm) 5/8
Liquid receiver dm³ 15
Length of connection piping m 50
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 13
Maximum quantity of evaporators connected Qty. 10
Evaporation temperature (Min) °C -15
Evaporation temperature (Max) °C 10
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Condenser .
Fans x diameter mm 1x560
Air flow (Nominal) m³/h 9.000
Fan static pressure Pa 120
Fan power supply V / ph / Hz 200 - 277 / 1 / 50
Fan power consumption W 1050
Nominal fan amperage A 4,6
Compressor - additional data .
Compressor model C-SBS180H00B/ C-SBN303H8G
Volumetric flow m³/h 5,8 - 17,4 / 11,6
Rotation range rps 32 - 90
Current (Full load amperage) A 14,7 / 8,0
Current (Peak current limit / Locked rotor amperage) A 34 / 48
Oil type FV68S (PVE)
Crankcase heater power consumption W 2x70
CU power supply .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x6,0
Recommended minimum protection C32

Complementary products

Mis uudist?