Specifications

See all
iCOOL SCU Series – MT
19.00 kW
Model SCU-KSC190M08
Compressors Tandem compressor
Compatible refrigerants R448A, R449A, R134a, R513A
PED CAT II
Application and nominal cooling capacity MT/LT (kW) MT (19,0)
MT (R449A/R448A) - Cooling capacity at .
ET -15°C, AT 32°C (Min - Max) kW 2,3 - 15,2
ET -15°C, AT 38°C (Min - Max) kW 2,1 - 13,5
ET -15°C, AT 43°C (Min - Max) kW — - —
ET -10°C, AT 32°C (Min - Max) kW 2,9 - 18,7
ET -10°C, AT 38°C (Min - Max) kW 2,6 - 16,7
ET -10°C, AT 43°C (Min - Max) kW 2,4 - 15,2
ET -5°C, AT 32°C (Min - Max) kW 3,6 - 22,7
ET -5°C, AT 38°C (Min - Max) kW 3,2 - 20,5
ET -5°C, AT 43°C (Min - Max) kW 3,0 - 18,8
MT (R134a/R513A) - Cooling capacity at .
ET -15°C; AT 32°C (Min - Max) kW 1,7 - 10,7
ET -15°C; AT 38°C (Min - Max) kW — - —
ET -15°C; AT 43°C (Min - Max) kW — - —
ET -10°C; AT 32°C (Min - Max) kW 2,2 - 13,1
ET -10°C; AT 38°C (Min - Max) kW 2,0 - 11,9
ET -10°C; AT 43°C (Min - Max) kW 1,9 - 11,5
ET -5°C; AT 32°C (Min - Max) kW 2,8 - 15,6
ET -5°C; AT 38°C (Min - Max) kW 2,6 - 14,6
ET -5°C; AT 43°C (Min - Max) kW 2,4 - 14,5
SEPR cooling at ET -10°C AT 32°C 3,19
SEPR freezing at ET -35°C AT 32°C
Annual electricity consumption at ET -10°C AT 32°C kWh/a 35.312
Annual electricity consumption at ET -35°C AT 32°C kWh/a
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 28,7
Maximum operating current (in the most loaded phase at 230 - 400V 50Hz) A 34,9
Maximum power consumption kW 17,7
Dimension (Width) mm 1.327
Dimension (Height) mm 1.558
Dimension (Depth) mm 745
Net weight kg 344
Sound level at 10m dB(A) 55,0
Oil charge dm³ 2,0 + 1,7 + 2x0,4
Connections (Suction) Inch (mm) 1 1/8
Connections (Liquid) Inch (mm) 5/8
Liquid receiver dm³ 15
Length of connection piping m 50
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 13
Maximum quantity of evaporators connected Qty. 10
Evaporation temperature (Min) °C -15
Evaporation temperature (Max) °C 10
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Condenser .
Fans x diameter mm 1x560
Air flow (Nominal) m³/h 9.000
Fan static pressure Pa 80
Fan power supply V / ph / Hz 200 - 277 / 1 / 50
Fan power consumption W 1.050
Nominal fan amperage A 4,6
Compressor - additional data .
Compressor model C-SBS180H00B/ C-SBN453H8G
Volumetric flow m³/h 5,8 - 17,4 / 14,7
Rotation range rps 32 - 90
Current (Full load amperage) A 15,2 / 11,9
Current (Peak current limit / Locked rotor amperage) A 34 / 66
Oil type FV68S (PVE)
Crankcase heater power consumption W 2x70
CU power supply .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x10,0
Recommended minimum protection C40