iCOOL SCU Series – LT

iCOOL SCU Series for LT applications

Models with high pressure fan for indoor mounting.

A Plug & Play HFO/HFC solution designed specifically for indoor installations.
This compact unit helps minimize installation time and reduce overall costs compared to central systems with remote condensers.

Specifications

See all
iCOOL SCU Series – LT THREE PHASE
9.00 kW
Model SCU-KSC090L08
Compressors Single compressor
Compatible refrigerants R448A, R449A
PED CAT II
Application and nominal cooling capacity MT/LT (kW) LT (9,0)
LT (R449A/R448A) - Cooling capacity at .
ET -35°C, AT 32°C (Min - Max) kW 1,7 - 6,8
ET -35°C, AT 38°C (Min - Max) kW 1,4 - 6,3
ET -35°C, AT 43°C (Min - Max) kW 1,2 - 5,9
ET -30°C, AT 32°C (Min - Max) kW 2,2 - 8,5
ET -30°C, AT 38°C (Min - Max) kW 1,9 - 7,9
ET -30°C, AT 43°C (Min - Max) kW 1,6 - 7,4
ET -25°C, AT 32°C (Min - Max) kW 2,8 - 10,6
ET -25°C, AT 38°C (Min - Max) kW 2,5 - 9,9
ET -25°C, AT 43°C (Min - Max) kW 2,2 - 9,3
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 23,0
Maximum operating current (in the most loaded phase at 230 - 400V 50Hz) A 32,5
Maximum power consumption kW 14,1
Dimension (Width) mm 1.327
Dimension (Height) mm 1.558
Dimension (Depth) mm 745
Net weight kg 325
Sound level at 10m dB(A) 55,0
Oil charge dm³ 2,5 + 0,4
Connections (Suction) Inch (mm) 1 1/8
Connections (Liquid) Inch (mm) 5/8
Liquid receiver dm³ 15
Length of connection piping m 40
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 19
Maximum quantity of evaporators connected Qty. 5
Evaporation temperature (Min) °C -35
Evaporation temperature (Max) °C -10
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Condenser
Fans x diameter mm 1x560
Air flow (Nominal) m³/h 9.000
Fan static pressure Pa 120
Fan power supply V / ph / Hz 200 - 277 / 1 / 50
Fan power consumption W 1.050
Nominal fan amperage A 4,6
Compressor - additional data
Compressor model ACC144NA03
Volumetric flow m³/h 10,0 - 37,6
Rotation range rps 25 - 72
Current (Full load amperage) A 22,9
Current (Peak current limit / Locked rotor amperage) A 46 / —
Oil type FV32S (PVE)
Crankcase heater power consumption W 90
CU power supply
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x10,0
Recommended minimum protection C40