3.50 kW. Wall Mounted Professional -20°C • R410A

KIT-E12-PKEA (CS-E12PKEA + CU-E12PKEA)

Complete line-up with high efficiency even at -20 °C.
This wall-mounted air conditioner is especially designed for professional applications such as computer rooms where cooling inside the room is necessary even when the outside temperature is low. Furthermore this air conditioner has an automatic changeover system, in order to maintain the inside temperature even when sharp outside temperature changes occur.

Specifications

See all
Wall Mounted Professional -20°C • R410A Single Phase
3.50 kW
EER (Nominal) (1) W/W 4,02 (3,57 - 5,00) A
COP (Nominal) (1) W/W 4,35 (3,63 - 5,15) A
Kit KIT-E12-PKEA
Cooling capacity (Nominal) kW 3,50
Cooling capacity (Min) kW 0,85
Cooling capacity (Max) kW 4,00
EER (Nominal) (1) W/W 4,02
EER (Min) (1) W/W 3,57
EER (Max) (1) W/W 5,00
Cooling capacity at -10°C kW 3,69
EER at -10°C W/W 5,96
Cooling capacity at -20°C kW 3,66
EER at -20°C W/W 5,56
SEER (2) 6,70 A++
Pdesign (cooling) kW 3,50
Input power cooling (Nominal) kW 0,87
Input power cooling (Min) kW 0,17
Input power cooling (Max) kW 1,12
Annual energy consumption cooling (3) kWh/a 183,00
Heating capacity (Nominal) kW 4,00
Heating capacity (Min) kW 0,85
Heating capacity (Max) kW 6,60
Heating capacity at -7°C (4) kW 4,07
COP (Nominal) (1) W/W 4,35
COP (Min) (1) W/W 3,63
COP (Max) (1) W/W 5,15
SCOP (5) 4,10 A+
Pdesign at -10°C kW 3,60
Input power heating (Nominal) kW 0,92
Input power heating (Min) kW 0,17
Input power heating (Max) kW 1,82
Annual energy consumption heating (3) kWh/a 1229
Indoor unit CS-E12PKEA
Indoor power source V 230
Indoor recommended fuse A 16
Indoor connection indoor / outdoor mm² 4 x 1,5
Indoor air flow (Cool) m³/min 13,6
Indoor air flow (Heat) m³/min 14,7
Moisture removal volume L/h 2,0
Indoor sound pressure (Cool -Hi) (5) dB(A) 42
Indoor sound pressure (Cool -Lo) (5) dB(A) 29
Indoor sound pressure (Cool -Q-Lo) (5) dB(A) 26
Indoor sound pressure (Heat -Hi) (5) dB(A) 42
Indoor sound pressure (Heat -Lo) (5) dB(A) 33
Indoor sound pressure (Heat -Q-Lo) (5) dB(A) 29
Indoor dimension (Height) mm 295
Indoor dimension (Width) mm 870
Indoor dimension (Depth) mm 255
Indoor net weight kg 10
Outdoor unit CU-E12PKEA
Outdoor sound pressure (Cool -Hi) (5) dB(A) 48
Outdoor sound pressure (Heat -Hi) (5) dB(A) 50
Outdoor dimension (Height) (6) mm 622
Outdoor dimension (Width) (6) mm 824
Outdoor dimension (Depth) (6) mm 299
Outdoor net weight kg 36
Pipe diameter (Liquid) Inch (mm) 1/4 (6,35)
Pipe diameter (Gas) Inch (mm) 3/8 (9,52) 
Pipe length range m 3
Elevation difference (in/out) (8) m 15
Pipe length for additional gas m 5
Additional gas amount g/m 7,5
Refrigerant (R410A) / CO2 Eq. kg / T 20
Operating range (Cool - Min) °C -20
Operating range (Cool - Max) °C 43
Operating range (Heat - Min) °C -15
Operating range (Heat - Max) °C 24

Complementary products