PACi NX Series Elite adaptívna kanálová jednotka Inverter+ - R32

14.0kW

KIT-140PF3ZH48 (S-1014PF3E + U-140PZH4E8)

Rozsah konštrukčného potrubia PF3

2 možnosti inštalácie (horizontálne / vertikálne) s vysokým ESP 150Pa umožňujú flexibilnú inštaláciu.

* Výkonnosť systému nanoe™ X air možno podľa interného prieskumu spoločnosti Panasonic očakávať aj pri 10 m dlhom potrubí.

Špecifikácie

Pozri všetky
PACi NX Series Elite adaptívna kanálová jednotka Inverter+ - R32
14.0 kW
Input power heating (Min) kW 0,77
Outdoor sound power (Heat -Hi) dB(A) 74
Outdoor sound power (Cool -Hi) dB(A) 74
Outdoor sound pressure (Heat - Hi) dB(A) 56
Outdoor sound pressure (Cool - Hi) dB(A) 56
Elevation difference (in/out) (8) m 15 / 30
Outdoor air flow (Heat) m³/min 83,0
Outdoor air flow (Cool) m³/min 89,0
nanoe X Generator Mark 2
Moisture removal volume L/h 36,0
Input power heating (Max) kW 5,55
Remote controller CZ-RTC5B
COP (Max) (1) W/W 4,29
COP (Min) (1) W/W 3,14
Heating capacity (Max) kW 17,4
Heating capacity (Min) kW 3,3
Annual energy consumption cooling (3) kWh/a
Input power cooling (Max) kW 5,90
Input power cooling (Min) kW 0,79
Input power cooling (Nominal) kW 3,96
Pdesign (cooling) kW 13,4
Indoor air flow (Med) m³/min 25,0
SCOP/ηs,h (2) % 162,6%
SEER/ηs,c (2) % 275,2%
Indoor sound pressure (Lo) (5) dB(A) 29
Indoor sound pressure (Med) (5) dB(A) 35
Indoor sound pressure (Hi) (5) dB(A) 39
External static pressure (Max) (4) Pa 150
External static pressure (Min) (4) Pa 10
External static pressure (Nominal) (4) Pa 50
Indoor air flow (Lo) m³/min 4,9
EER (Max) (1) W/W 4,18
Indoor air flow (Hi) m³/min 32,0
Indoor sound power (Lo) dB(A) 52
Indoor sound power (Med) dB(A) 58
Current in heating (1p 240V / 3p 415) A 7,05
Current in heating (1p 230V / 3p 400) A 7,40
Current in heating (1p 220V / 3p 380) A 7,75
Current in cooling (1p 240V / 3p 415) A 6,00
Current in cooling (1p 230V / 3p 400) A 6,20
Current in cooling (1p 220V / 3p 380) A 6,55
Indoor net weight kg 39
COP (Nominal) (1) W/W 3,33
Outdoor power source V 380 - 400 - 415
Heating capacity (Nominal) kW 15,5
Cooling capacity (Nominal) kW 13,4
Operating range (Cool - Min) °C -20 (9)
Input power heating (Nominal) kW 4,65
Pdesign at -10°C kW 9,5
Annual energy consumption heating (3) kWh/a
Outdoor net weight kg 84
Outdoor dimension (Height) mm 996
EER (Nominal) (1) W/W 3,38
Indoor dimension (Height) mm 250
Pipe length range m 5 ~ 100
Additional gas amount g/m 40
EER (Min) (1) W/W 2,59
Cooling capacity (Max) kW 15,3
Cooling capacity (Min) kW 3,3
Operating range (Heat - Max) °C +24
Operating range (Heat - Min) °C -20
Operating range (Cool - Max) °C +52
Outdoor unit U-140PZH4E8
Indoor unit S-1014PF3E
Kit KIT-140PF3ZH48
Pre-charged pipe length m 30
Piping diameter (Gas) Inch (mm) 5/8 (15,88)
Piping diameter (Liquid) Inch (mm) 3/8 (9,52)
Outdoor dimension (Depth) mm 370
Outdoor dimension (Width) mm 980
Indoor dimension (Depth) mm 730
Indoor dimension (Width) mm 1.400
Refrigerant (R32) / CO2 Eq. kg / T 3,00 / 2,03
Indoor sound power (Hi) dB(A) 62

1) Výpočet EER a COP je založený na norme EN14511.
2) Pri modeloch s výkonom nižším ako 12 kW sa SEER a SCOP vypočítavajú na základe hodnôt EÚ/626/2011. Pre modely nad 12 kW sa hodnoty ηs,c / ηs,h vypočítavajú na základe normy EN 14825.
3) Nastavenie z výroby.
4) Stredný vonkajší statický tlak nastavený z výroby.
5) Akustický tlak jednotiek uvádza hodnotu nameranú z miesta 1,5 m pod jednotkou. Akustický tlak sa meria v súlade so špecifikáciou Eurovent 6/C/006-97.
6) Pripojte rúrku kvapalinovej zásuvky (Ø6,35-Ø9,52) k vnútornej jednotke na strane kvapalinovej rúrky.
7) K vnútornej jednotke na strane plynovej rúrky pripojte plynovú nátrubkovú rúrku (Ø12,70-Ø15,88). 8) Vonkajšia jednotka umiestnená nižšie / vonkajšia jednotka umiestnená vyššie.
9) Dĺžka potrubia do 30 m.
* Odporúčaná poistka pre vnútornú jednotku 3A.

** Vyššie uvedené hodnoty sú v prípade štandardnej inštalácie (horizontálna inštalácia v obložení, prívod vzduchu zo zadnej strany) a nanoe™ X OFF.