Fan coil mural Aquarea Air Smart
1.61kW
P-FMM15
Fan coil Aquarea Air Smart para montaje en pared
- Perfil de chasis delgado, sólo 128 mm
- RAL 9003
- Inversor de CC: maximiza el confort y el ahorro de energía
- Flujo de aire modulado
- Conexiones de agua izquierda o derecha
- Válvulas de 2 ó 3 vías como accesorios
- Control integrado o montado en la pared o PCB para entrada analógica (0-10V)
Especificaciones
| Fan coil mural Aquarea Air Smart | |||
|---|---|---|---|
| 1.61 kW | |||
| Modelo | P-FMM15 | ||
| Fan speed (1) | Min / Med / Max | ||
| Total cooling capacity (Min) (2) | kW | 0,62 | |
| Total cooling capacity (Med) (2) | kW | 1,08 | |
| Total cooling capacity (Max) (2) | kW | 1,61 | |
| Sensible capacity (Min) (2) | kW | 0,52 | |
| Sensible capacity (Med) (2) | kW | 0,86 | |
| Sensible capacity (Max) (2) | kW | 1,27 | |
| Water flow cooling (Min) (2) | l/h | 106,20 | |
| Water flow cooling (Med) (2) | l/h | 185,00 | |
| Water flow cooling (Max) (2) | l/h | 275,80 | |
| Water pressure drop cooling (Min) (2) | kPa | 4,7 | |
| Water pressure drop cooling (Med) (2) | kPa | 5,6 | |
| Water pressure drop cooling (Max) (2) | kPa | 5,1 | |
| Heating capacity (Min) (3) | kW | 0,76 | |
| Heating capacity (Med) (3) | kW | 1,30 | |
| Heating capacity (Max) (3) | kW | 1,93 | |
| Water flow heating (Min) (3) | l/h | 139,30 | |
| Water flow heating (Med) (3) | l/h | 239,80 | |
| Water flow heating (Max) (3) | l/h | 354,40 | |
| Water pressure drop heating (Min) (3) | kPa | 4,8 | |
| Water pressure drop heating (Med) (3) | kPa | 6,3 | |
| Water pressure drop heating (Max) (3) | kPa | 7,2 | |
| Niveles sonoros | . | ||
| Sound power (Min) | dB(A) | 36 | |
| Potencia acústica (Med) | dB(A) | 47 | |
| Sound power (Max) | dB(A) | 54 | |
| Sound pressure (Min) (4) | dB(A) | 25 | |
| Sound pressure (Med) (4) | dB(A) | 34 | |
| Sound pressure (Max) (4) | dB(A) | 41 | |
| Ventilation | . | ||
| Air flow (Min) | m³/h | 124 | |
| Caudal de aire (Med) | m³/min | 229 | |
| Caudal de aire (máx.) | m³/h | 331 | |
| Datos eléctricos | . | ||
| Suministro eléctrico (voltaje) | V | 230 | |
| Suministro eléctrico (fase) | 1 | ||
| Suministro eléctrico (frecuencia) | Hz | 50 | |
| Consumption (Min) | W | 5 | |
| Consumption (Med) | W | 9 | |
| Consumption (Max) | W | 20 | |
| Conexiones de agua de los fan coils | . | ||
| Hydraulic connections type | Eurokonus | ||
| Hydraulic connections | Inch | ¾ | |
| Dimensiones y peso | . | ||
| Dimensiones (Altura) | mm | 335 | |
| Dimensiones (Anchura) | mm | 1.015 | |
| Dimensiones (Profundidad) | mm | 128 | |
| Peso neto | kg | 16 | |
1) Velocidades estándar del ventilador ajustadas en fábrica.
2) Según norma Eurovent. Aire: 27°C DB/19°C WB, agua fría: 7°C/12°C.
3) Según norma Eurovent. Aire: 20°C, agua caliente: 45°C/40°C.
4) Datos informativos, considerando una hipotética atenuación acústica del local y de la instalación de 9dB(A).