12.5 kW
Kit KIT-125PT2ZH5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 12,5
Cooling capacity (Min) kW 3,2
Cooling capacity (Max) kW 14,0
EER (Nominal) (1) W/W 3,45
SEER (2) 6,6
Pdesign (cooling) kW 12,5
Input power cooling (Nominal) kW 3,62
Annual energy consumption cooling (3) kWh/a
Annual energy consumption cooling (3) kWh/a
Heating capacity (Nominal) kW 14,0
Heating capacity (Min) kW 3,2
Heating capacity (Max) kW 16,0
COP (Nominal) (1) W/W 3,99
SCOP (2) 4,4
Pdesign at -10°C kW 9,5
Input power heating (Nominal) kW 3,51
Annual energy consumption heating (3) kWh/a
Indoor unit S-125PT2E5B
Indoor air flow (Hi) m³/min 34,0
Indoor air flow (Med) m³/min 28,0
Indoor air flow (Lo) m³/min 24,0
Indoor sound pressure (Med) (4) dB(A) 40
Indoor sound pressure (Lo) (4) dB(A) 36
Indoor dimension (Height) mm 235
Indoor dimension (Width) mm 1590
Indoor dimension (Depth) mm 690
Indoor net weight kg 40
Outdoor unit U-125PZH2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 16,80
Current in cooling (1p 230V / 3p 400) A 16,00
Current in cooling (1p 240V / 3p 415) A 15,40
Current in heating (1p 220V / 3p 380) A 16,20
Current in heating (1p 230V / 3p 400) A 15,50
Current in heating (1p 240V / 3p 415) A 14,90
Outdoor air flow (Cool) m³/min 125
Outdoor air flow (Heat) m³/min 122
Outdoor sound pressure (Cool -Hi) dB(A) 53
Outdoor sound pressure (Heat -Hi) dB(A) 53
Outdoor sound power (Cool -Hi) dB(A) 70
Outdoor sound power (Heat -Hi) dB(A) 70
Outdoor dimension (Height) mm 1416
Outdoor dimension (Width) mm 940
Outdoor dimension (Depth) mm 340
Outdoor net weight kg 99
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 85
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 45
Refrigerant (R32) / CO2 Eq. kg / T 3,05 / 2,059
Operating range (Cool - Min) °C -20 (6)
Operating range (Cool - Max) °C 46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C 24

(1) Izračun EER in COP je izdelan na podlagi EN14511.
(2) Lestvica energijskih nalepk od A+++ do D. Za modele z manj kot 12 kW sta vrednosti SEER in SCOP izračunani na podlagi vrednosti direktive EU/626/2011. Za modele z več kot 12 kW sta vrednosti SEER in SCOP izračunani na podlagi vrednosti direktive EU/2281/2016.
(3) Letna poraba energije je izračunana v skladu z direktivo EU/626/2011.
(4) Zvočni tlak enot prikazuje vrednost, izmerjeno 1 meter pred glavnim ohišjem in 1 meter pod enoto. Zvočni tlak je izmerjen v skladu s tehničnimi navedbami v dokumentu Eurovent 6/C/006-97.
(5) Pri nameščanju zunanje enote na višji položaj od notranje enote.
(6) Modeli 100–140PZH2E5(8) lahko v računalniških prostorih delujejo pri temperaturi do –20 °C z dolžino cevi 30 m ali manj.
* Priporočena jakost varovalke za notranjo enoto je 3 A.