iCOOL WCU Series – LT

iCOOL WCU Series for LT applications

The variation of iCOOL to meet demanding installation environment requirements.

High performance inverter water/glycol-cooled condensing unit for commercial installations. Designed for LT applications. Equipped with hermetic scroll or rotary compressor. Perfect for low noise and city center applications.

  • Noise reduction (indoor installation)
  • No space pollution (city-centres focus)

Equipped with factory-assembled water/glycol-cooled PHE condenser, for shorter installations and heat reclaim benefits.

Specifications

See all
iCOOL WCU Series – LT THREE PHASE
2.0 kW 3.0 kW 5.4 kW 8.7 kW
Model WCU-KRC020L08 WCU-KRC035L08 WCU-KRC050L08 WCU-KSC090L08
Compressors Single compressor Single compressor Single compressor Single compressor
Compatible refrigerants R448A, R449A R448A, R449A R448A, R449A R448A, R449A
PED CAT I I I II
Application and nominal cooling capacity MT/LT (kW) LT (2,0) LT (3,0) LT (5,4) LT (8,7)
LT (R449A/R448A) - Cooling capacity at . . . .
ET -35°C, WT 15°C, CT 30°C (Min - Max) kW 0,3 - 2,2 0,4 - 3,3 1,2 - 5,8 2,6 - 8,2
ET -35°C, WT 30°C, CT 40°C (Min - Max) kW 0,2 - 1,7 0,3 - 2,6 1,1 - 4,6 2,0 - 7,3
ET -35°C, WT 40°C, CT 50°C (Min - Max) kW — - — — - — — - — — - —
ET -30°C, WT 15°C, CT 30°C (Min - Max) kW 0,4 - 2,7 0,5 - 4,0 1,5 - 7,1 3,3 - 10,1
ET -30°C, WT 30°C, CT 40°C (Min - Max) kW 0,3 - 2,2 0,4 - 3,3 1,4 - 5,8 2,6 - 9,1
ET -30°C, WT 40°C, CT 50°C (Min - Max) kW 0,2 - 1,8 0,3 - 2,8 1,2 - 5,0 2,0 - 8,3
ET -25°C, WT 15°C, CT 30°C (Min - Max) kW 0,5 - 3,4 0,7 - 4,9 1,9 - 8,7 4,2 - 12,6
ET -25°C, WT 30°C, CT 40°C (Min - Max) kW 0,4 - 2,8 0,5 - 4,1 1,7 - 7,3 3,3 - 11,4
ET -25°C, WT 40°C, CT 50°C (Min - Max) kW 0,3 - 2,3 0,4 - 3,5 1,5 - 6,3 2,6 - 10,3
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 400V 50Hz A 3,9 6,1 11,7 18,9
Maximum operating current (in the most loaded phase at 400V 50Hz) A 5,7 8,4 14,9 27,9
Maximum power consumption kW 2,7 3,9 7,0 13,1
Dimension (Width) mm 1.000 1.000 1.000 1.300
Dimension (Height) mm 705 705 772 705
Dimension (Depth) mm 530 530 536 530
Net weight kg 92 92 139 169
Sound level at 10m dB(A) 39,0 42,0 50,0 55,0
Oil charge dm³ 0,7 + 0,4 0,7 + 0,4 2,1 + 0,4 2,5 + 0,4
Connections (Suction) Inch (mm) 5/8 7/8 7/8 1 1/8
Connections (Liquid) Inch (mm) 3/8 3/8 3/8 5/8
Liquid receiver dm³ 3,9 3,9 7,1 14
Length of connection piping m 40 40 40 40
Maximum height distance (Evaporator above) m 12 12 12 12
Maximum height distance (Evaporator below) m 12 12 12 12
Which pipes needs to be insulated (Suction / liquid / both) Suction Suction Suction Suction
Recommended insulation thickness mm 13 19 19 19
Maximum quantity of evaporators connected Qty. 5 5 5 5
Evaporation temperature (Min) °C -35 -35 -35 -35
Evaporation temperature (Max) °C 5 -15 -15 -10
Ambient temperature (Min) °C -20 -20 -20 -20
Ambient temperature (Max) °C 43 43 43 43
Plate heat exchanger connections (Inlet) Inch 3/4 1/2 1/2 1
Plate heat exchanger connections (Outlet) Inch 3/4 3/4 3/4 1
Compressor - additional data . . . .
Compressor model C-7RVN113L0A C-7RZ320L4ABL C-9RZ580L4AAL ACC144NA03
Volumetric flow m³/h 1,25 - 7,5 1,7 - 10,4 5,2 - 18,7 10,0 - 37,6
Rotation range rps 15 - 90 15 - 90 25 - 90 25 - 72
Current (Full load amperage) A 4,4 6,4 10 22,9
Current (Peak current limit / Locked rotor amperage) A 11,2 / — 15 / — 28 / — 46 / —
Oil type FV68S (PVE) FV68S (PVE) FV68S (PVE) FV32S (PVE)
Crankcase heater power consumption W 35 35 35 2x90
CU power supply . . . .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S) 3x400 / 50 PE+N (TN-S) 3x400 / 50 PE+N (TN-S) 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x2,5 5x2,5 5x4,0 5x6,0
Recommended minimum protection C16 C16 C25 C32

* ET: Evaporating Temperature. WT: Water (or glycol Inlet Temperature. CT: Condensing Temperature.