NX Series Jet Air Stream

5.000m³/h

KIT-250MC5AZH8

PACi NX Jet Air Stream

Energy-saving solution for year-round heating and cooling in large and high

High air distribution for large spaces
· High air volume up to 5000m³/h
· Long maximum air throw distance of 30m

Optimal comfort with Smart Jet - self-directing nozzles
· Precise temperature control
· Preventing stratification and maintaining an ideal temperature exclusively in the occupied area

Specifications

See all
NX Series Jet Air Stream
5.000 m³/h
Kit KIT-250MC5AZH8
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 24,2
Cooling capacity (Min) kW 6,1
Cooling capacity (Max) kW 25,6
EER (Nominal) (1) W/W 3,80
EER (Min) (1) W/W 2,49
EER (Max) (1) W/W 4,88
ηs,c (2) % 250%
Pdesign (cooling) kW —
Heating capacity (Nominal) kW 26,7
Heating capacity (Min) kW 5,5
Heating capacity (Max) kW 27,6
COP (Nominal) (1) W/W 3,74
COP (Min) (1) W/W 3,07
COP (Max) (1) W/W 4,78
ηs,h (2) 155%
Pdesign at -10°C kW 18,5
Model Jet Air Stream Smart
Indoor unit P-VTVF250MC5A-PE
Nozzles type Smart Jet - self-directing nozzles
Number of nozzles 4
External static pressure Pa 170
Air flow m³/h 5.010
Indoor sound pressure (Cool) (3) dB(A) 46
Indoor sound pressure (Heat) (3) dB(A) 46
Indoor dimension (Height) mm 1 041
Indoor dimension (Width) mm 1 458
Indoor dimension (Depth) mm 930
Indoor net weight kg 140
Outdoor unit U-250PZH4E8
Power supply (Voltage) V 380 - 400 - 415
Power supply (Phase) Three phase
Power supply (Frequency) Hz 50
Recommended fuse A 30
Outdoor sound pressure (Cool -Hi) dB(A) 59
Outdoor sound pressure (Heat -Hi) dB(A) 63
Outdoor dimension (Height) mm 996
Outdoor dimension (Width) mm 1.140
Outdoor dimension (Depth) mm 460
Outdoor net weight kg 109
Pipe diameter (Liquid) Inch (mm) 1/2 (12,70)
Pipe diameter (Gas) Inch (mm) 7/8 (22,22)
Pipe length range m 5 ~ 100
Elevation difference (in/out) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 80
Refrigerant (R32) / CO2 Eq. kg / T 4,80 / 3,24
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C +52
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C +35

1) EER and COP calculation is based in accordance to EN 14511.
2) Average sound pressure at 5m Lp.
3) Radiated sound power at 5m Lp.
4) Outdoor unit located lower / outdoor unit located higher.
5) Pipe length up to 30m.
* Tentative data.

What's happening