NX Series Jet Air Stream
25.0kW
KIT-250MC5ZH8
PACi NX Jet Air Stream
Energy-saving solution for year-round heating and cooling in large and high
· High air volume up to 5000m³/h
· Long maximum air throw distance of 30m
Optimal comfort with Smart Jet - self-directing nozzles
· Precise temperature control
· Preventing stratification and maintaining an ideal temperature exclusively in the occupied area
Specifications
| NX Series Jet Air Stream | |||
|---|---|---|---|
| 25.0 kW | |||
| Power supply (Voltage) | V | 380 - 400 - 415 | |
| Operating range (Cool - Max) | °C | +52 | |
| Operating range (Heat - Min) | °C | -20 | |
| Operating range (Heat - Max) | °C | +35 | |
| Cooling capacity (Min) | kW | 6,1 | |
| Cooling capacity (Max) | kW | 25,6 | |
| EER (Min) (1) | W/W | 2,49 | |
| EER (Max) (1) | W/W | 4,88 | |
| Heating capacity (Min) | kW | 5,5 | |
| Heating capacity (Max) | kW | 27,6 | |
| COP (Min) (1) | W/W | 3,07 | |
| COP (Max) (1) | W/W | 4,78 | |
| Outdoor dimension (Width) | mm | 1.140 | |
| Outdoor dimension (Depth) | mm | 460 | |
| Elevation difference (in/out) | m | 30 | |
| Outdoor unit | U-250PZH4E8 | ||
| Power supply (Phase) | Three phase | ||
| Power supply (Frequency) | Hz | 50 | |
| Outdoor sound pressure (Cool -Hi) | dB(A) | 59 | |
| Outdoor sound pressure (Heat -Hi) | dB(A) | 63 | |
| Remote controller | PCZ-AHRX0012 | ||
| Air flow | m³/min | 5.000 | |
| External static pressure | Pa | 170 | |
| Recommended fuse | A | 30 | |
| Operating range (Cool - Min) | °C | -15 | |
| Pipe length range | m | 5 ~ 100 | |
| Indoor dimension (Height) | mm | 1.026 | |
| Indoor net weight | kg | 97 | |
| Outdoor dimension (Height) | mm | 996 | |
| Outdoor net weight | kg | 109 | |
| Cooling capacity (Nominal) | kW | 22,0 | |
| Heating capacity (Nominal) | kW | 24,0 | |
| COP (Nominal) (1) | W/W | 3,55 | |
| EER (Nominal) (1) | W/W | 2,74 | |
| Refrigerant (R32) / CO2 Eq. | kg / T | 4,80 / 3,24 | |
| Indoor dimension (Width) | mm | 1.360 | |
| Indoor dimension (Depth) | mm | 953 | |
| Pipe diameter (Liquid) | Inch (mm) | 1/2 (12,70) | |
| Pipe diameter (Gas) | Inch (mm) | 7/8 (22,22) | |
| Pipe length for additional gas | m | 30 | |
| Additional gas amount | g/m | 80 | |
| Kit | KIT-250MC5ZH8 | ||
| Indoor unit | P-VTVF250MC5-PE | ||
1) EER and COP calculation is based in accordance to EN 14511.
2) Average sound pressure at 5m Lp.
3) Radiated sound power at 5m Lp.
4) Outdoor unit located lower / outdoor unit located higher.
5) Pipe length up to 30m.
* Tentative data.