8.7 kW
Model LCU-KSC090L08
Compressors Single compressor
Compatible refrigerants R448A, R449A
PED CAT II
Application and nominal cooling capacity MT/LT (kW) LT (8,7)
LT (R449A/R448A) - Cooling capacity at .
ET -35°C, CT 40°C (Min - Max) kW 2,0 - 7,3
ET -35°C, CT 45°C (Min - Max) kW 1,8 - 6,9
ET -35°C, CT 50°C (Min - Max) kW — - —
ET -30°C, CT 40°C (Min - Max) kW 2,6 - 9,1
ET -30°C, CT 45°C (Min - Max) kW 2,3 - 8,7
ET -30°C, CT 50°C (Min - Max) kW 2,0 - 8,3
ET -25°C, CT 40°C (Min - Max) kW 3,3 - 11,4
ET -25°C, CT 45°C (Min - Max) kW 3,0 - 10,9
ET -25°C, CT 50°C (Min - Max) kW 2,6 - 10,3
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 18,9
Maximum operating current (in the most loaded phase at 400V 50Hz) A 27,9
Maximum power consumption kW 13,1
Dimension (Width) mm 1.300
Dimension (Height) mm 705
Dimension (Depth) mm 530
Net weight kg 159
Sound level at 10m dB(A) 55,0
Oil charge dm³ 2,5 + 0,4
Connections (Suction) Inch (mm) 1 1/8
Connections (Liquid) Inch (mm) 5/8
Liquid receiver dm³ 14
Length of connection piping m 40
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 19
Maximum quantity of evaporators connected Qty. 5
Evaporation temperature (Min) °C -35
Evaporation temperature (Max) °C -10
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Compressor - additional data .
Compressor model ACC144NA03
Volumetric flow m³/h 10,0 - 37,6
Rotation range rps 25-72
Current (Full load amperage) A 22,9
Current (Peak current limit / Locked rotor amperage) A 46 / —
Oil type FV32S (PVE)
Crankcase heater power consumption W 2x90
CU power supply .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x6,0
Recommended minimum protection C32