iCOOL SE Series – LT

Previous capacity Next capacity

1.20kW

OCU-KRE012L05

iCOOL SE Series. Simple Engineering solution for LT applications

From 1,2 to 3,0kW.

Easy to install, with a simplified commissioning process. Inverter technology has never been this easy.

Save time and operation cost with our energy-efficient units based on Inverter compressors.

Specifications

See all
iCOOL SE Series – LT
1.20 kW
Model OCU-KRE012L05
Compressors Single compressor
Compatible refrigerants R448A, R449A
PED CAT I
Application and nominal cooling capacity MT/LT (kW) LT (1,2)
LT (R449A/R448A) - Cooling capacity at .
ET -35°C, AT 32°C (Min - Max) kW 0,3 - 1,0
ET -35°C, AT 38°C (Min - Max) kW 0,3 - 0,9
ET -35°C, AT 43°C (Min - Max) kW 0,2 - 0,8
ET -30°C, AT 32°C (Min - Max) kW 0,4 - 1,2
ET -30°C, AT 38°C (Min - Max) kW 0,3 - 1,1
ET -30°C, AT 43°C (Min - Max) kW 0,3 - 1,0
ET -25°C, AT 32°C (Min - Max) kW 0,5 - 1,5
ET -25°C, AT 38°C (Min - Max) kW 0,4 - 1,4
ET -25°C, AT 43°C (Min - Max) kW 0,4 - 1,3
SEPR freezing at ET -35°C AT 32°C (R448A)
Annual electricity consumption at ET -35°C AT 32°C (R448A) kWh/a
COP at ET -35°C, AT 32°C (R448A) 0,95
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 5,5
Maximum operating current (in the most loaded phase at 230 - 400V 50Hz) A 7,2
Maximum power consumption kW 1,4
Dimension (Width) mm 1.000
Dimension (Height) mm 605
Dimension (Depth) mm 450
Net weight kg 70
Sound level at 10m dB(A) 42,5
Connections (Suction) Inch (mm) 1/2
Connections (Liquid) Inch (mm) 3/8
Liquid receiver dm³ 3,9
Length of connection piping m 20
Maximum height distance (Evaporator above) m 7
Maximum height distance (Evaporator below) m 7
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 19
Maximum quantity of evaporators connected Qty. 3
Evaporation temperature (Min) °C -35
Evaporation temperature (Max) °C -15
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Condenser .
Fans x diameter mm 1x450
Air flow (Nominal) m³/h 3.600
Fan power supply V / ph / Hz 220 - 240 / 1 / 50
Fan power consumption W 170
Nominal fan amperage A 1,4
Compressor - additional data .
Compressor model C-6RVN63L0B
Volumetric flow m³/h 0,6 - 4,1
Rotation range rps 30 - 90
Current (Full load amperage) A 3,6
Current (Peak current limit / Locked rotor amperage) A 15 / —
Oil type FV68S
Oil compressor charge dm³ 0,6
Crankcase heater power consumption W 35
CU power supply .
Voltage V / ph / Hz 220 - 240 / 1 / 50
Recommended minimum cable cross-section mm² 3x2,5
Recommended minimum protection C16