U - 050/060/070/075 CM, CN, CO
75.3kW
U-075CMNB / U-075CMBM / U-075CNNB / U-075CNBM / U-075CONB / U-075COBM
ECOi-W R32 Heat Pump Chiller
Cooling capacity: 49,9 to 75,3kW.
Heating capacity: 53,5 to 80,0kW.
High seasonal efficiency in cooling, maximum SEER 4,54 in this range. ECOi-W Series offers a variety of options to meet your needs.
· High seasonal efficiency in cooling and heating
· Eurovent certified
· Ambient temperature operating range: -15 to +48°C in cooling, -15 to +20°C in heating
· Water outlet temperature range: -10 to +18°C in cooling, +20 to +55°C in heating
· Optional acoustically insulating compressor jacket
· Optimised design for service and maintenance
· Simple user friendly control as standard
· Modbus RTU & TCP/IP, BACnet MSTP & IP as standard
· Electronic expansion valves
Technical focus.
· Chiller type: heat pump
· Compressor type (number): Scroll compressors (2)
· Refrigerant type: R32
· Refrigerant circuit: 1
· Fan type (number): axial fan (1 for 50/60, 2 for 70/75), optional EC and high pressure EC fans
· Heat exchanger: stainless steel plate heat exchanger
· Flow switch, water safety & air purge valves included
· Water filter included (mandatory to be installed on site)
· Night mode setting to save energy and reduce noise level
· Water compensation curve control
· Bluefin anti-corrosion coating
The reasons to choose Panasonic as your partner
Explore the new range of fan coils
Specifications
| U - 050/060/070/075 CM, CN, CO | |||
|---|---|---|---|
| 75.3 kW | |||
| AC fan model without buffer / with buffer | U-075CMNB / U-075CMBM | ||
| EC fan model without buffer / with buffer | U-075CNNB / U-075CNBM | ||
| High pressure EC fan model without buffer / with buffer | U-075CONB / U-075COBM | ||
| Power supply (Voltage) | V | 400 | |
| Power supply (Phase) | Three phase | ||
| Power supply (Frequency) | Hz | 50 | |
| Cooling capacity (1) | kW | 75,3 | |
| Input power cooling (1) | kW | 25,7 | |
| Total EER 100% (1) | 2,93 | ||
| SEER (2) (3) | 4,47 | ||
| ηs,c (2) (3) | % | 176 | |
| Heating capacity (4) | kW | 80,0 | |
| Input power heating (4) | kW | 24,7 | |
| SCOP (3) (5) | 3,57 | ||
| ηs,h (3) (5) | % | 140 | |
| Energy efficiency class (Scale A+++ to D) (6) | - | ||
| Startup type | Direct | ||
| Maximum operating current | A | 69,4 | |
| Startup current without softstarter | A | 209 | |
| Startup current with softstarter | A | 157 | |
| Sound power (with AC / EC fans) | dB(A) | 81,3 | |
| Sound pressure (with AC / EC fans) (7) | dB(A) | 49,5 | |
| Sound power (with HP EC fans) | dB(A) | 89,3 | |
| Sound pressure (with HP EC fans) (7) | dB(A) | 57,5 | |
| Dimension (with AC fans) without buffer (Height) | mm | 1.986 | |
| Dimension (with AC fans) without buffer (Width) | mm | 2.180 | |
| Dimension (with AC fans) without buffer (Depth) | mm | 1.160 | |
| Dimension (with AC fans) with buffer (Height) | mm | 1.986 | |
| Dimension (with AC fans) with buffer (Width) | mm | 2.680 | |
| Dimension (with AC fans) with buffer (Depth) | mm | 1.160 | |
| Dimension (with EC / HP EC fans) without buffer (Height) | mm | 2.034 | |
| Dimension (with EC / HP EC fans) without buffer (Width) | mm | 2.180 | |
| Dimension (with EC / HP EC fans) without buffer (Depth) | mm | 1.160 | |
| Dimension (with EC / HP EC fans) with buffer (Height) | mm | 2.034 | |
| Dimension (with EC / HP EC fans) with buffer (Width) | mm | 2.680 | |
| Dimension (with EC / HP EC fans) with buffer (Depth) | mm | 1.160 | |
| Operating weight without buffer | kg | 637 | |
| Operating weight with buffer | kg | 1.130 | |
| Refrigerant (R410A) | kg | 10,6 | |
| Number of refrigerant circuit | 1 | ||
| Compressors | . | ||
| Number of compressors | 2 | ||
| Type of compressors | Scroll | ||
| Part load step | % | 0 /46 /54 /100 | |
| Crankcase heater | W | 66 /66 | |
| Evaporator | . | ||
| Number of evaporators | 1 | ||
| Type of evaporators | Plate | ||
| Nominal water flow (cooling) | m³/h | 13,2 / 13,9 | |
| Water pressure drop (cooling) | kPa | 38,2 / 42,8 | |
| Water volume | L | 6,1 | |
| Antifreeze heater | W | 2 x 30 | |
| Coils | . | ||
| Number of coils | 2 | ||
| Frontal surface | m² | 5,6 | |
| Number of rows | 2 | ||
| Fans standard | . | ||
| Number of fans standard | 2 | ||
| Air flow (AC fan) | m³/h | 30.000 | |
| Rotation speed (AC fan) | r.p.m. | 690 | |
| Power input (AC fan each fan) | W | 1,0 | |
| Air flow (EC fan) | m³/h | 30.000 | |
| Rotation speed (EC fan) | r.p.m. | 620 | |
| Power input (EC fan each fan) | W | 0,6 | |
| Air flow (HP EC fans) | m³/h | 30.000 | |
| Rotation speed (HP EC fans) | r.p.m. | 940 | |
| Power input (HP EC fans each fan) | W | 1,9 | |
| Static pressure | Pa | 180 | |
| Water connections | Inch | . | |
| Type of water connections | Male gas threaded BSPP ISO 228 | ||
| Inlet - diameter (evaporator) | Inch | 2 | |
| Outlet - diameter (evaporator) | Inch | 2 | |
| Inlet - diameter (desuperheater) | Inch | 1 ¼ | |
| Outlet - diameter (desuperheater) | Inch | 1 ¼ | |
1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers.
3) Those are the data with variable flow.
4) Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.
5) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps.
6) Following Eurovent and COMMISSION REGULATION (EU) No 811/2013 for low-temperature heat pumps. Scale from A+++ to D, as of 26th September 2019.
7) Sound pressure levels calculated at 10 meters. Sound pressure levels refer to ISO standard 3744 with parallel piped shape.