Models
Aquarea Air Smart fan coil wall-mounted
- Slim chassis profile, only 128mm
- RAL 9003
- DC Inverter – maximising comfort and energy savings
- Modulated air flow
- Left or right water connections
- 2 or 3 way valves as accessories
- On-board or wall mounted control or PCB for analog input (0-10V)
Self-modulated air flow control by the unit (PI logic)
The fan speed is no longer “stepped” but continuously modulated with proportional and integrative logic: this reduces both noise and annoying air movements.
Specifications
| Aquarea Air Smart fan coil wall‑mounted | SINGLE PHASE | ||||
|---|---|---|---|---|---|
| 1.24 kW | 1.61 kW | 3.94 kW | |||
| Model | P-FMM10 | P-FMM40 | |||
| Fan speed (1) | Min / Med / Max | Min / Med / Max | |||
| Total cooling capacity (Min) (2) | kW | 0,49 | 1,32 | ||
| Total cooling capacity (Med) (2) | kW | 0,88 | 2,66 | ||
| Total cooling capacity (Max) (2) | kW | 1,24 | 3,94 | ||
| Sensible capacity (Min) (2) | kW | 0,37 | 1,08 | ||
| Sensible capacity (Med) (2) | kW | 0,70 | 2,05 | ||
| Sensible capacity (Max) (2) | kW | 0,98 | 2,92 | ||
| Water flow cooling (Min) (2) | l/h | 84,00 | 226,40 | ||
| Water flow cooling (Med) (2) | l/h | 150,80 | 455,30 | ||
| Water flow cooling (Max) (2) | l/h | 212,40 | 674,30 | ||
| Water pressure drop cooling (Min) (2) | kPa | 4,8 | 1,8 | ||
| Water pressure drop cooling (Med) (2) | kPa | 10,5 | 6,0 | ||
| Water pressure drop cooling (Max) (2) | kPa | 11,7 | 12,1 | ||
| Heating capacity (Min) (3) | kW | 0,54 | 1,63 | ||
| Heating capacity (Med) (3) | kW | 0,98 | 3,04 | ||
| Heating capacity (Max) (3) | kW | 1,45 | 4,44 | ||
| Water flow heating (Min) (3) | l/h | 97,00 | 296,40 | ||
| Water flow heating (Med) (3) | l/h | 176,30 | 547,00 | ||
| Water flow heating (Max) (3) | l/h | 264,50 | 800,90 | ||
| Water pressure drop heating (Min) (3) | kPa | 5,1 | 2,3 | ||
| Water pressure drop heating (Med) (3) | kPa | 12,0 | 6,9 | ||
| Water pressure drop heating (Max) (3) | kPa | 16,3 | 14,1 | ||
| Sound levels | . | . | |||
| Sound power (Min) | dB(A) | 35 | 38 | ||
| Sound power (Med) | dB(A) | 46 | 47 | 48 | |
| Sound power (Max) | dB(A) | 53 | 62 | ||
| Sound pressure (Min) (4) | dB(A) | 25 | 27 | ||
| Sound pressure (Med) (4) | dB(A) | 33 | 37 | ||
| Sound pressure (Max) (4) | dB(A) | 40 | 51 | ||
| Ventilation | . | . | |||
| Air flow (Min) | m³/h | 84 | 230 | ||
| Air flow (Med) | m³/min | 155 | 229 | 480 | |
| Air flow (Max) | m³/h | 228 | 331 | 788 | |
| Electrical data | . | . | |||
| Power supply (Voltage) | V | 230 | 230 | 230 | |
| Power supply (Phase) | 1 | 1 | 1 | ||
| Power supply (Frequency) | Hz | 50 | 50 | 50 | |
| Consumption (Min) | W | 5 | 8 | ||
| Consumption (Med) | W | 8 | 23 | ||
| Consumption (Max) | W | 19 | 30 | ||
| Fan coils water connections | . | . | |||
| Hydraulic connections type | Eurokonus | Eurokonus | |||
| Hydraulic connections | Inch | ¾ | ¾ | ||
| Dimensions and weight | . | . | |||
| Dimension (Height) | mm | 335 | 335 | 335 | |
| Dimension (Width) | mm | 815 | 1.015 | 1.215 | |
| Dimension (Depth) | mm | 128 | 128 | 215 | |
| Net weight | kg | 14 | 16 | 24 | |
1) Fan standard factory set speeds.
2) According to Eurovent standard. Air: 27°C DB/19°C WB, chilled water: 7°C/12°C.
3) According to Eurovent standard. Air: 20°C, hot water: 45°C/40°C.
4) Informative data, considering an hypothetical sound attenuation of the room and installation of 9dB(A).