Air Curtain LS and HS type with DX Coil

Air curtain with DX Coil, connected to the VRF or PACi Systems

Compatible with R32 or R410A outdoor units.

High efficiency air curtain connected to your PACi or VRF installation. EC Fan motor for a smooth operation and an efficient performance. 2 types of air flow available: LS and HS! Easy installation, regulation, cleaning, service.
  • Save up to 40% energy costs by use of the integrated EC fan technology (higher efficiency than conventional AC fan, soft start and longer motor duration)
  • 4 length of air curtain LS and HS are available 1,0, 1,5, 2,0 and 2,5m
  • Installation height up to 3,0m
  • Outlet grilles can be adjusted in five positions, to suite different indoor and installation requirements
  • Control with Panasonic remote control systems (optional)
  • Direct integration to BMS by optional Panasonic interfaces
  • Trip dray included in all DX air curtain steps

Specifications

See all
Air Curtain LS and HS type with DX Coil SINGLE PHASE
61 kW 91 kW 97 kW 130 kW 130 kW 170 kW 195 kW 237 kW
Outdoor unit 7,1kW 10,0kW 10,0kW 14,0kW 14,0kW 20,0kW 20,0kW 25,0kW
Reference PAW-10PAIRC-LS PAW-10PAIRC-HS PAW-15PAIRC-LS PAW-15PAIRC-HS PAW-20PAIRC-LS PAW-25PAIRC-LS PAW-20PAIRC-HS PAW-25PAIRC-HS
Air outlet height m 2,7 3,0 2,7 3,0 2,7 2,7 3,0 3,0
Air flow (Hi) m³/min 1800 2700 2700 3600 3600 4500 5400 6300
Cooling capacity (Max) (1) kW 6,1 9,1 9,7 13,0 13,0 17,0 19,5 23,7
Heating capacity (Max) (2) kW 7,9 11,8 12,0 15,8 15,0 19,0 23,6 27,6
Heat exchanger (Volume) L 1,67 1,67 2,85 2,85 3,94 5,03 3,94 5,12
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88) 5/8 (15,88) 3/4 (19,05) 3/4 (19,05) 7/8 (22,22) 7/8 (22,22) 7/8 (22,22) 7/8 (22,22)
Electric consumption fan (230V / 50Hz) kW 0,30 0,75 0,50 1,00 0,60 0,80 1,50 1,75
Fan type EC EC EC EC EC EC EC EC
Current (230V / 50Hz) A 2,10 4,10 3,10 5,50 4,10 5,10 8,20 9,60
Sound pressure (Max) (3) dB(A) 65 66 66 67 67 69 68 68
Dimension (Height) (4) mm 260 (+140) 260 (+140) 260 (+140) 260 (+140) 260 (+140) 260 (+140) 260 (+140) 260 (+140)
Dimension (Width) (4) mm 1000 1000 1500 1500 2000 2500 2000 2500
Dimension (Depth) (4) mm 460 460 460 460 460 460 460 460
Net weight kg 50 55 65 65 80 95 85 110
Door width m 1,0 1,0 1,5 1,5 2,0 2,5 2,0 2,5
Refrigerant R32 / R410A R32 / R410A R32 / R410A R32 / R410A R32 / R410A R32 / R410A R32 / R410A R32 / R410A
(1) Cooling capacity DX Coil, air temperature in/out +27/+18°C, R32 and R410.

(2) Heating capacity condenser, air temperature in/out +20/+33°C, R32 and R410. In the case of lower outdoor temperatures, an outdoor model with higher capacity may be necessary.
(3) Measured in distance up to 5,0m, direction factor 2, absorbing surfaces 200m², Min / Max Air flow.
(4) 140mm is the height of an electrical box if it is installed on the top.

Rated Conditions Cooling Outdoor +35°C DB Indoor +27°C DB/+19°C WB, Discharge temperature 16°C. All combinations under rated conditions: Heating Outdoor +7°C DB/+6°C WB Indoor +20°C DB. In case of lower outdoor temperatures a higher capacity outdoor unit model may be necessary.