PACi Elite Low Static Pressure Hide Away • R32

The depth of only 250mm provides greater installation flexibility and the unit can be used in more applications. Ideal for sites with narrow ceiling voids.

Ultra-slim profile: 250mm height for all models.

  • Automatic learning function for the required static pressure on site during commissioning (a standard wired remote controller is required. S-60/71/100/125/140PN1E5B models only)
  • Compact indoor units without loosing static pressure (only 250 mm high)
  • 50 Pa static pressure
  • Easy maintenance and service via external electrical box
  • 3 speed centrifugal fan through wired or Infrared remote controller
  • DC FAN for better efficiency and control
  • Easy connection and control of external fan or ERV using the connector PAW-FDC on the indoor unit PCB. The external device can be controlled by the remote control of the Panasonic indoor unit

Specifications

See all
PACi Elite Low Static Pressure Hide Away • R32 SINGLE PHASE THREE PHASE
36 kW 50 kW 60 kW 71 kW 100 kW 125 kW 140 kW 71 kW 100 kW 125 kW 140 kW
EER (Nominal) (1) W/W 3,85 3,35 3,40 3,40 3,95 3,35 3,15 3,40 3,95 3,35 3,15
COP (Nominal) (1) W/W 4,40 3,35 3,75 3,68 3,90 3,70 3,50 3,68 3,90 3,70 3,50
Refrigerant (R32) / CO2 Eq. kg / T
Kit KIT-36PN1ZH5 KIT-50PN1ZH5 KIT-60PN1ZH5 KIT-71PN1ZH5 KIT-100PN1ZH5 KIT-125PN1ZH5 KIT-140PN1ZH5 KIT-71PN1ZH8 KIT-100PN1ZH8 KIT-125PN1ZH8 KIT-140PN1ZH8
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity (Nominal) kW 3,6 5,0 6,0 7,1 10,0 12,5 14,0 7,1 10,0 12,5 14,0
Cooling capacity (Min) kW 1,5 1,5 2,0 2,0 3,1 3,2 3,3 2,2 3,1 3,2 3,3
Cooling capacity (Max) kW 4,0 5,6 7,1 9,0 12,5 14,0 16,0 9,0 12,5 14,0 16,0
EER (Nominal) (1) W/W 3,85 3,40 3,41 3,40 3,95 3,35 3,15 3,40 3,95 3,35 3,15
SEER (2) 5,1 A 5,1 A 6,0 A+ 6,0 A+ 6,0 A+ 6 5,8 5,9 A+ 5,9 A+ 5,9 5,8
Pdesign (cooling) kW 3,6 5,0 6,0 7,1 10,0 12,5 14,0 7,1 10,0 12,5 14,0
Input power cooling (Nominal) kW 0,93 1,47 1,76 2,09 2,53 3,73 4,45 2,09 2,53 3,73 4,45
Annual energy consumption cooling (3) kWh/a 246 342 350 414 582 418 588
Heating capacity (Nominal) kW 4,0 5,6 7,0 8,0 11,2 14,0 16,0 8,0 11,2 14,0 16,0
Heating capacity (Min) kW 1,5 1,5 1,8 2,0 3,1 3,3 3,3 2,0 3,1 3,3 3,3
Heating capacity (Max) kW 5,0 6,5 7,0 9,0 14,0 16,0 18,0 9,0 14,0 16,0 18,0
COP (Nominal) (1) W/W 4,40 3,50 3,80 3,90 4,00 3,70 3,50 3,90 4,00 3,70 3,60
SCOP (2) 4,0 A+ 4,0 A+ 4,0 A+ 4,0 A+ 4,0 A+ 3,9 3,8 4,0 A+ 4,0 A+ 3,9 3,8
Pdesign at -10°C kW 3,6 3,8 5,6 5,2 8,0 9,5 10,6 5,2 8,0 9,5 10,6
Input power heating (Nominal) kW 0,91 1,60 1,84 2,05 2,80 3,78 4,45 2,05 2,80 3,78 4,45
Annual energy consumption heating (3) kWh/a 1258 1573 2095 1914 2799 1914 2799
Indoor unit S-36PN1E5B S-50PN1E5B S-60PN1E5B S-71PN1E5B S-100PN1E5B S-125PN1E5B S-140PN1E5B S-71PN1E5B S-100PN1E5B S-125PN1E5B S-140PN1E5B
External static pressure (Nominal) (4) Pa 25 25 25 25 40 50 50 25 40 50 50
External static pressure (Min) (4) Pa 10 10 10 10 10 10 10 10 10 10 10
External static pressure (Max) (4) Pa 80 80 80 80 80 80 80 80 80 80 80
Indoor air flow (Hi) m³/min 14,0 16,0 22,0 22,0 36,0 38,0 40,0 22,0 36,0 38,0 46,0
Indoor air flow (Lo) m³/min 12,0 13,0 20,0 20,0 33,0 35,0 37,0 20,0 33,0 35,0 37,0
Moisture removal volume L/h 10,0 10,0  16,0 16,0 26,0 28,0 30,0 16,0 26,0 28,0 30,0
Indoor sound pressure (Hi) (5) dB(A) 35 36 38 38 39 40 41 38 39 40 41
Indoor sound pressure (Med) (5) dB(A) 33 34 36 36 37 38 39 36 37 38 39
Indoor sound pressure (Lo) (5) dB(A) 30 30 31 31 32 33 34 31 32 33 34
Indoor dimension (Height) mm 250 250 250 250 250 250 250 250 250 250 250
Indoor dimension (Width) mm 780 780 1000 1000 1200 1200 1200 1000 1200 1200 1200
Indoor dimension (Depth) mm 650 650 650 650 650 650 650 650 650 650 650
Indoor net weight kg 29 29 32 32 41 41 41 32 41 41 41
Outdoor unit U-36PZH2E5 U-50PZH2E5 U-60PZH2E5 U-71PZH2E5 U-100PZH2E5 U-125PZH2E5 U-140PZH2E5 U-71PZH2E8 U-100PZH2E8 U-125PZH2E8 U-140PZH2E8
Outdoor power source V 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 4,20 6,50 8,20 9,45 11,20 16,90 20,00 3,20 3,75 5,65 11,70
Current in cooling (1p 230V / 3p 400) A 4,00 6,20 7,85 9,00 10,70 16,10 19,30 3,05 3,55 5,40 11,20
Current in cooling (1p 240V / 3p 415) A 3,85 5,95 7,50 8,60 10,20 15,40 18,40 2,95 3,45 5,20 10,70
Current in heating (1p 220V / 3p 380) A 4,10 7,15 8,60 9,20 2,40 17,00 20,20 3,20 4,20 5,75 6,80
Current in heating (1p 230V / 3p 400) A 3,90 6,85 8,25 8,85 11,90 16,20 19,30 2,95 4,00 5,45 6,45
Current in heating (1p 240V / 3p 415) A 3,75 6,55 7,85 8,45 11,40 15,60 18,50 2,85 3,85 5,25 6,20
Outdoor air flow (Cool) m³/min 40 40 40 61 118 125 129 61 118 125 129
Outdoor air flow (Heat) m³/min 40 45 45 60 108 122 116 60 108 112 116
Outdoor sound pressure (Cool -Hi) dB(A) 43 45 46 48 52 53 54 48 52 53 54
Outdoor sound pressure (Heat -Hi) dB(A) 44 48 49 50 52 53 54 50 52 53 54
Outdoor sound power (Cool -Hi) dB(A) 62 64 65 65 69 70 71 65 69 70 71
Outdoor sound power (Heat -Hi) dB(A) 64 68 69 67 69 70 71 67 69 70 71
Outdoor dimension (Height) mm 695 695 695 996 1416 1416 1416 996 1416 1416 1416
Outdoor dimension (Width) mm 875 875 875 940 940 940 940 940 940 940 940
Outdoor dimension (Depth) mm 320 320 320 340 340 340 340 340 340 340 340
Outdoor net weight kg 43 43 44 68 99 99 99 68 99 99 99
Pipe diameter (Liquid) Inch (mm) 1/4 (6,35) 1/4 (6,35) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 1/2 (12,70) 1/2 (12,70) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
Pipe length range m 3 ~ 40 3 ~ 40 3 ~ 40 5 ~ 50 5 ~ 85 5 ~ 85 5 ~ 85 5 ~ 50 5 ~ 85 5 ~ 85 5 ~ 85
Elevation difference (in/out) (6) m 30 30 30 30 30 30 30 30 30 30 30
Pipe length for additional gas m 30 30 30 30 30 30 30 30 30 30 30
Additional gas amount g/m 20 20 35 45 45 45 45 45 45 45 45
Refrigerant (R32) / CO2 Eq. kg / T 1,15 / 0,776 1,15 / 0,776 1,45 / 0,979 1,95 / 1,316 3,05 / 2,059 3,05 / 2,059 3,05 / 2,059 1,95 / 1,316 3,05 / 2,059 3,05 / 2,059 3,05 / 2,059
Operating range (Cool - Min) °C -15 -15 -15 -15 -20 (7) -20 (7) -20 (7) -15 -20 (7) -20 (7) -20 (7)
Operating range (Cool - Max) °C 46 46 46 46 46 46 46 46 46 46 46
Operating range (Heat - Min) °C -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20
Operating range (Heat - Max) °C 24 24 24 24 24 24 24 24 24 24 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Medium external static pressure setting from factory.
(5) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(6) When installing the outdoor unit at a higher position than the indoor unit.
(7) For models 100 ~ 140PZH2E5(8), it is possible to operate the lowest -20 °C in the computer rooms with the piping length of 30 m or less.
* Recommended fuse for the indoor 3 A.

Complementary products