PACi Standard Wall-Mounted • R32 Einphasig Dreiphasig
6.1 kW 7.1 kW 9.0 kW 9.0 kW
Kit KIT-60PK2Z5 KIT-71PK2Z5 KIT-100PK2Z5 KIT-100PK2Z8
Remote controller CZ-RTC5B CZ-RTC5B CZ-RTC5B CZ-RTC5B
Cooling capacity (Nominal) kW 6,1 7,1 9,0 9,0
Cooling capacity (Min) kW 2,0 2,0 3,0 3,0
Cooling capacity (Max) kW 7,1 7,7 9,7 9,7
EER (Nominal) (1) W/W 3,79 3,21 3,47 3,47
EER (Min) (1) W/W 5,36 5,36
EER (Max) (1) W/W 3,13 3,13 
SEER (2) 6,8 A++ 6,4 A++ 6,5 A++ 6,5 A++
Pdesign (cooling) kW 6,1 7,1 9,0 9,0
Input power cooling (Nominal) kW 1,61 2,21 2,59 2,59
Input power cooling (Min) kW 0,56 0,56
Input power cooling (Max) kW 3,10 3,10
Annual energy consumption cooling (3) kWh/a 314 388 485 485
Heating capacity (Nominal) kW 6,1 7,1 9,0 9,0
Heating capacity (Min) kW 1,8 1,8 3,0 3,0
Heating capacity (Max) kW 7,0 8,1 10,5 10,5
COP (Nominal) (1) W/W 4,80 4,41 3,93 3,93
COP (Min) (1) W/W 5,36 5,36
COP (Max) (1) W/W 3,56 3,56 
SCOP (2) 4,7 A++ 4,6 A++ 3,9 A 3,9 A
Pdesign at -10°C kW 6,0 6,0 9,0 9,0
Input power heating (Nominal) kW 1,27 1,61 2,29 2,29
Input power heating (Min) kW 0,56 0,56
Input power heating (Max) kW 2,95 2,95
Annual energy consumption heating (3) kWh/a 1787 1826 3231 3231
Indoor unit S-60PK2E5B S-71PK2E5B S-100PK2E5B S-100PK2E5B
Indoor air flow (Hi) m³/min 20,0 20,0 22,0 22,0
Indoor air flow (Med) m³/min 18,0 18,0 18,5 18,5
Indoor air flow (Lo) m³/min 15,0 15,0 15,0 15,0
Moisture removal volume L/h 2,0 3,0 4,3 4,3
Indoor sound pressure (Med) (4) dB(A) 44 44 45 45
Indoor sound pressure (Lo) (4) dB(A) 40 40 41 41
Indoor sound power (Hi) dB(A) 63 63 65 65
Indoor sound power (Med) dB(A) 60 60 61 61
Indoor sound power (Lo) dB(A) 56 56 57 57
Indoor dimension (Height) mm 302 302 302 302
Indoor dimension (Width) mm 1120 1120 1120 1120
Indoor dimension (Depth) mm 236 236 236 236
Indoor net weight kg 14 14 14 14
Outdoor unit U-60PZ2E5 U-71PZ2E5 U-100PZ2E5 U-100PZ2E8
Outdoor power source V 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 7,85 10,70 12,10 4,10
Current in cooling (1p 230V / 3p 400) A 7,50 10,20 11,50 3,90
Current in cooling (1p 240V / 3p 415) A 7,20 9,85 11,10 3,75
Current in heating (1p 220V / 3p 380) A 6,10 7,85 10,60 3,60
Current in heating (1p 230V / 3p 400) A 5,85 7,50 10,20 3,45
Current in heating (1p 240V / 3p 415) A 5,60 7,20 9,70 3,30
Outdoor air flow (Cool) m³/min 40 50 76 76
Outdoor air flow (Heat) m³/min 45 45 70 70
Outdoor sound pressure (Cool -Hi) dB(A) 46 49 52 52
Outdoor sound pressure (Heat -Hi) dB(A) 48 49 52 52
Outdoor sound power (Cool -Hi) dB(A) 65 69 70 70
Outdoor sound power (Heat -Hi) dB(A) 68 69 70 70
Outdoor dimension (Height) mm 695 695 996 996
Outdoor dimension (Width) mm 875 875 980 980
Outdoor dimension (Depth) mm 320 320 370 370
Outdoor net weight kg 44 44 90 90
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
Pipe length range m 3 ~ 40 3 ~ 40 5 ~ 50 5 ~ 50
Elevation difference (in/out) (5) m 30 30 30 30
Pipe length for additional gas m 30 30 30 30
Additional gas amount g/m 35 35 45 45
Refrigerant (R32) / CO2 Eq. kg / T 1,45 / 0,979 1,45 / 0,979 2,60 / 1,755 2,60 / 1,755
Operating range (Cool - Min) °C -10 -10 -10 -10
Operating range (Cool - Max) °C 43 43 43 43
Operating range (Heat - Min) °C -15 -15 -15 -15
Operating range (Heat - Max) °C 24 24 24 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1 m in front of the main body and 1 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.