PACi Standard from 7,1 to 14,0 kW. R32

Önceki kapasite Sonraki kapasitesi

10.0kW

U-100PZ3E5 / U-100PZ3E8

PACi Standard from 7,1 to 14,0 kW

Up to 2 indoor units connectable on the same outdoor. Panasonic’s PACi units can be installed as single and twin systems. The indoor units can be combined following the selection table. The operation will always be simultaneous. All the indoor units will work with the same settings.


Doğanın dengesini iç mekana getirir

Teknik Özellikler

Tümünü gör
PACi Standard from 7,1 to 14,0 kW. R32
10.0 kW
Outdoor unit single phase U-100PZ3E5
Outdoor unit three phase U-100PZ3E8
Cooling capacity (Nominal) kW 10,0 
Cooling capacity (Min) kW 3,0 
Cooling capacity (Max) kW 11,5 
Heating capacity (Nominal) kW 10,0 
Heating capacity (Min) kW 3,0 
Heating capacity (Max) kW 14,0 
Power supply (Single phase) V 220 - 230 - 240
Power supply (Three phase) V 380 - 400 - 415
Outdoor connection indoor / outdoor mm² 2x1,5 or 2,5
Air flow (Cool Hi) m³/min 73,0 
Air flow (Heat Hi) m³/min 73
Outdoor sound pressure (Cool -Hi) dB(A) 52 
Outdoor sound pressure (Heat -Hi) dB(A) 52
Outdoor sound power (Cool -Hi) dB(A) 70 
Outdoor sound power (Heat -Hi) dB(A) 70
Outdoor dimension (Height) mm 996 
Outdoor dimension (Width) mm 980 
Outdoor dimension (Depth) mm 370
Net weight kg 83
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 50
Elevation difference (in/out) m 15  / 30
Pipe length for additional gas m 30
Additional gas amount g/m 45
Refrigerant (R32) / CO2 Eq. kg / T 2,4 / 1,62
Operating range (Cool - Min) °C -10 
Operating range (Cool - Max) °C 43
Operating range (Heat - Min) °C -15 
Operating range (Heat - Max) °C 24