PZ super-compact • R32

Wall-mounted PZ super-compact Inverter.

PZ is a compact and quiet wall split series with high standards specs.

Discover the latest generation of air conditioning system

Manage your Panasonic solutions anytime, anywhere

Specifications

See all
PZ super-compact • R32 SINGLE PHASE
5 kW 2.5 kW 3.4 kW
Outdoor unit CU-PZ50WKE CU-PZ25WKE CU-PZ35WKE
Cooling capacity (Nominal) kW 5,00 2,50 3,40
Cooling capacity (Min) kW 0,98 0,85 0,85
Cooling capacity (Max) kW 5,40 3,00 3,90
EER (Nominal) (1) W/W 2,98 3,62 3,09
EER (Min) (1) W/W 3,92 4,05 3,54
EER (Max) (1) W/W 2,86 3,30 3,00
SEER (2) 6,00 A+ 6,00 A+ 6,00 A+
Pdesign (cooling) kW 5,00 2,50 3,40
Input power cooling (Nominal) kW 1,68 0,69 1,10
Input power cooling (Min) kW 0,25 0,21 0,24
Input power cooling (Max) kW 1,89 0,91 1,30
Annual energy consumption cooling (3) kWh/a 292,00 146,00 198,00
Heating capacity (Nominal) kW 5,40 3,15 3,84
Heating capacity (Min) kW 0,98 0,80 0,80
Heating capacity (Max) kW 7,50 3,60 4,40
Heating capacity at -7°C kW 4,58 2,14 2,60
COP (Nominal) (1) W/W 3,44 4,09 3,69
COP (Min) (1) W/W 4,67 4,21 4,10
COP (Max) (1) W/W 3,07 3,50 3,46
SCOP (2) 4,10 A+ 4,10 A+ 4,10 A+
Pdesign at -10°C kW 4,00 1,90 2,40
Input power heating (Nominal) kW 1,57 0,77 1,04
Input power heating (Min) kW 0,21 0,19 0,20
Input power heating (Max) kW 2,44 1,03 1,27
Annual energy consumption heating (3) kWh/a 1366 649 820
Outdoor sound pressure (Cool -Hi) (4) dB(A) 48 48 48
Outdoor sound pressure (Heat -Hi) (4) dB(A) 49 49 50
Outdoor dimension (Height) (5) mm 619 542 542
Outdoor dimension (Width) (5) mm 824 780 780
Outdoor dimension (Depth) (5) mm 299 289 289
Outdoor net weight kg 36 24 25
Pipe diameter (Liquid) Inch (mm) 1/4 (6,35) 1/4 (6,35) 1/4 (6,35)
Pipe diameter (Gas) Inch (mm) 1/2 (12,70) 3/8 (9,52) 3/8 (9,52)
Pipe length for additional gas m 7,5 7,5 7,5
Additional gas amount g/m 15 10 10
Refrigerant (R32) / CO2 Eq. kg / T 1,14 / 0,770 0,54 / 0,365 0,67 / 0,452
Operating range (Cool - Min) °C 5 5 5
Operating range (Cool - Max) °C +43 +43 +43
Operating range (Heat - Min) °C -15 -15 -15
Operating range (Heat - Max) °C +24 +24 +24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the indoor unit shows the value measured of a position 1 m in front of the main body and 0,8 m below the unit. For outdoor unit 1 m in front and 1 m in rear side of main body. The sound pressure is measured in accordance with JIS C 9612. Q-Lo: Quiet mode. Lo: The lowest set fan speed.
(5) Add 70 mm for piping port.
(6) When installing the outdoor unit at a higher position than the indoor unit.

Complementary products