iCOOL SE Series – LT
2.20kW
OCU-KRE022L05
iCOOL SE Series. Simple Engineering solution for LT applications
From 1,2 to 3,0kW.
Easy to install, with a simplified commissioning process. Inverter technology has never been this easy.
Save time and operation cost with our energy-efficient units based on Inverter compressors.
- Similar investment cost and significant energy savings vs. on-off technology
- Full BLDC Inverter technology
- Dedicated PLC controller
- Low noise operation
- Suitable for multi-evaporator applications (MT models)
- Designed and manufactured in Europe
Specifications
| iCOOL SE Series – LT | |||
|---|---|---|---|
| 2.20 kW | |||
| Model | OCU-KRE022L05 | ||
| Compressors | Single compressor | ||
| Compatible refrigerants | R448A, R449A | ||
| PED | CAT | I | |
| Application and nominal cooling capacity | MT/LT (kW) | LT (2,2) | |
| LT (R449A/R448A) - Cooling capacity at | . | ||
| ET -35°C, AT 32°C (Min - Max) | kW | 0,6 - 1,8 | |
| ET -35°C, AT 38°C (Min - Max) | kW | 0,5 - 1,6 | |
| ET -35°C, AT 43°C (Min - Max) | kW | 0,5 - 1,5 | |
| ET -30°C, AT 32°C (Min - Max) | kW | 0,7 - 2,2 | |
| ET -30°C, AT 38°C (Min - Max) | kW | 0,7 - 2,0 | |
| ET -30°C, AT 43°C (Min - Max) | kW | 0,6 - 1,9 | |
| ET -25°C, AT 32°C (Min - Max) | kW | 0,9 - 2,8 | |
| ET -25°C, AT 38°C (Min - Max) | kW | 0,8 - 2,5 | |
| ET -25°C, AT 43°C (Min - Max) | kW | 0,8 - 2,3 | |
| SEPR freezing at ET -35°C AT 32°C (R448A) | — | ||
| Annual electricity consumption at ET -35°C AT 32°C (R448A) | kWh/a | — | |
| COP at ET -35°C, AT 32°C (R448A) | 0,98 | ||
| Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz | A | 9,5 | |
| Maximum operating current (in the most loaded phase at 230 - 400V 50Hz) | A | 12,7 | |
| Maximum power consumption | kW | 2,6 | |
| Dimension (Width) | mm | 1.000 | |
| Dimension (Height) | mm | 605 | |
| Dimension (Depth) | mm | 450 | |
| Net weight | kg | 70 | |
| Sound level at 10m | dB(A) | 42,5 | |
| Connections (Suction) | Inch (mm) | 5/8 | |
| Connections (Liquid) | Inch (mm) | 3/8 | |
| Liquid receiver | dm³ | 3,9 | |
| Length of connection piping | m | 20 | |
| Maximum height distance (Evaporator above) | m | 7 | |
| Maximum height distance (Evaporator below) | m | 7 | |
| Which pipes needs to be insulated (Suction / liquid / both) | Suction | ||
| Recommended insulation thickness | mm | 19 | |
| Maximum quantity of evaporators connected | Qty. | 3 | |
| Evaporation temperature (Min) | °C | -35 | |
| Evaporation temperature (Max) | °C | -15 | |
| Ambient temperature (Min) | °C | -20 | |
| Ambient temperature (Max) | °C | 43 | |
| Condenser | . | ||
| Fans x diameter | mm | 1x450 | |
| Air flow (Nominal) | m³/h | 3.600 | |
| Fan power supply | V / ph / Hz | 220 - 240 / 1 / 50 | |
| Fan power consumption | W | 170 | |
| Nominal fan amperage | A | 1,4 | |
| Compressor - additional data | . | ||
| Compressor model | C-7RVN113L0B | ||
| Volumetric flow | m³/h | 1,25 - 7,5 | |
| Rotation range | rps | 30 - 90 | |
| Current (Full load amperage) | A | 7,1 | |
| Current (Peak current limit / Locked rotor amperage) | A | 25 / — | |
| Oil type | FV68S | ||
| Oil compressor charge | dm³ | 0,7 | |
| Crankcase heater power consumption | W | 35 | |
| CU power supply | . | ||
| Voltage | V / ph / Hz | 220 - 240 / 1 / 50 | |
| Recommended minimum cable cross-section | mm² | 3x2,5 | |
| Recommended minimum protection | C20 | ||