6.0 kW. PACi Standard Low Static Pressure Hide Away • R32

KIT-60PN1Z5 (S-60PN1E5B + U-60PZ2E5)

Предходна мощност Следваща мощност

The depth of only 250mm provides greater installation flexibility and the unit can be used in more applications. Ideal for sites with narrow ceiling voids.

Ultra-slim profile: 250mm height for all models.

  • Automatic learning function for the required static pressure on site during commissioning (a standard wired remote controller is required. S-60/71/100/125/140PN1E5B models only)
  • Compact indoor units without loosing static pressure (only 250 mm high)
  • 50 Pa static pressure
  • Easy maintenance and service via external electrical box
  • 3 speed centrifugal fan through wired or Infrared remote controller
  • DC FAN for better efficiency and control
  • Easy connection and control of external fan or ERV using the connector PAW-FDC on the indoor unit PCB. The external device can be controlled by the remote control of the Panasonic indoor unit

Спецификации

Вижте всички
PACi Standard Low Static Pressure Hide Away • R32 ЕДНОФАЗНИ
6.0 kW
EER (Nominal) (1) W/W 3,20
COP (Nominal) (1) W/W 3,80
Refrigerant (R32) / CO2 Eq. kg / T
Kit KIT-60PN1Z5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 6,0
Cooling capacity (Min) kW 2,0
Cooling capacity (Max) kW 7,1
EER (Nominal) (1) W/W 3,31
SEER (2) 5,8 A+
Pdesign (cooling) kW 6,0
Input power cooling (Nominal) kW 1,81
Annual energy consumption cooling (3) kWh/a 361
Heating capacity (Nominal) kW 6,0
Heating capacity (Min) kW 1,8
Heating capacity (Max) kW 7,0
COP (Nominal) (1) W/W 3,90
SCOP (2) 4,0 A+
Pdesign at -10°C kW 5,6
Input power heating (Nominal) kW 1,54
Annual energy consumption heating (3) kWh/a 2095
Indoor unit S-60PN1E5B
External static pressure (Nominal) (4) Pa 25
External static pressure (Min) (4) Pa 10
External static pressure (Max) (4) Pa 80
Indoor air flow (Hi) m³/min 22,0
Indoor air flow (Med) m³/min 20,0
Indoor air flow (Lo) m³/min 16,0
Indoor sound pressure (Hi) (5) dB(A) 38
Indoor sound pressure (Med) (5) dB(A) 36
Indoor sound pressure (Lo) (5) dB(A) 31
Indoor dimension (Height) mm 250
Indoor dimension (Width) mm 1000
Indoor dimension (Depth) mm 650
Indoor net weight kg 32
Outdoor unit U-60PZ2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 8,30
Current in cooling (1p 230V / 3p 400) A 8,00
Current in cooling (1p 240V / 3p 415) A 7,60
Current in heating (1p 220V / 3p 380) A 7,00
Current in heating (1p 230V / 3p 400) A 6,70
Current in heating (1p 240V / 3p 415) A 6,40
Outdoor air flow (Cool) m³/min 40
Outdoor air flow (Heat) m³/min 45
Outdoor sound pressure (Cool -Hi) dB(A) 46
Outdoor sound pressure (Heat -Hi) dB(A) 48
Outdoor sound power (Cool -Hi) dB(A) 65
Outdoor sound power (Heat -Hi) dB(A) 68
Outdoor dimension (Height) mm 695
Outdoor dimension (Width) mm 875
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 44
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 3 ~ 40
Elevation difference (in/out) (6) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 35
Refrigerant (R32) / CO2 Eq. kg / T 1,45 / 0,979
Operating range (Cool - Min) °C -10
Operating range (Cool - Max) °C 43
Operating range (Heat - Min) °C -15
Operating range (Heat - Max) °C 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Medium external static pressure setting from factory.
(5) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(6) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.

Допълнителни продукти

Реални примери Вижте всички проекти

Какво се случва