PACi Elite High Static Pressure Hide Away • R410A
10.0kW
KIT-100PF1E8D (S-100PF1E5B + U-100PE1E8A)
The ducted systems are the ideal solution for flexible, concealed air conditioning and the optional 200 mm spigots ensure simple, hassle-free connection to spiral ductwork.
- High ESP (external static pressure) up to 150 Pa
- Automatic learning function for the required static pressure on site during commissioning (a standard wired remote controller is required)
- DC FAN for better efficiency and control
- Built in drain pump
- Datanavi simple support tool App with remote controller (CZ-RTC5B)
- Twin split options
- Easy connection and control of external fan or ERV using the connector PAW-FDC on the indoor unit PCB. The external device can be controlled by the remote control of the Panasonic indoor unit
Широка гама от продукти за търговски обекти,
офиси или жилищни сгради
Системи въздух-въздух за търговски обекти
Широка гама от продукти за търговски обекти,
офиси или жилищни сгради
Системи въздух-въздух за търговски обекти
Спецификации
| PACi Elite High Static Pressure Hide Away • R410A | |||
|---|---|---|---|
| 10.0 kW | |||
| EER (номинален) (1) | W/W | 4,10 (3,93 - 3,38) A | |
| COP (номинален) (1) | W/W | 4,31 (4,56 - 3,18) A | |
| EER (номинален) (1) | W/W | 4,10 (3,93 - 3,38) A | |
| Мощност на отопление при -7 °C (2) | kW | — | |
| Мощност на отопление при -15 °C (2) | kW | — | |
| COP (номинален) (1) | W/W | 4,31 (4,56 - 3,18) A | |
| Външно статично налягане (Номинално) (5) | Pa | 100 | |
| Външно статично налягане (Мин.) (5) | Pa | 10 | |
| Външно статично налягане (Макс.) (5) | Pa | 150 | |
| Звуково налягане на вътрешното тяло (В) (6) | dB(A) | 38 | |
| Звуково налягане на вътрешното тяло (Ср.) (6) | dB(A) | 34 | |
| Звуково налягане на вътрешното тяло (Н) (6) | dB(A) | 31 | |
| Денивелация (вътр./външно) (7) | m | 30 | |
| Хладилен агент (R410A)/CO2 екв. | kg / T | 3,40 / 7,0992 | |
(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Heating capacity is calculated including defrost factor correction.
(5) Medium external static pressure setting from factory.
(6) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(7) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.