iCO2RE NCU CO₂ Series Einphasig
0.7 kW 1.8 kW
Model NCU-CTC009L05* NCU-CTC018M05
Compressors 2-stufiger Kompressor 2-stufiger Kompressor
Refrigerant R744 R744
PED CAT Ich Ich
Application and nominal cooling capacity MT/LT (kW) LT MT
Spannungsversorgung (V) V 230 / PE+N (TN-S) 230 / PE+N (TN-S)
Spannungsversorgung (ph) 1 1
Spannungsversorgung (Hz) Hz 50 50
MT - Cooling capacity at . .
ET -15°C, AT 32°C (Min - Max) kW — 1,38
ET -15°C, AT 38°C (Min - Max) kW — 1,28
ET -15°C, AT 43°C (Min - Max) kW — 1,20
ET -10°C, AT 32°C (Min - Max) kW — 1,78
ET -10°C, AT 38°C (Min - Max) kW — 1,48
ET -10°C, AT 43°C (Min - Max) kW — 1,38
ET -5°C, AT 32°C (Min - Max) kW — 2,02
ET -5°C, AT 38°C (Min - Max) kW — 1,78
ET -5°C, AT 43°C (Min - Max) kW — 1,46
LT - Cooling capacity at . .
ET -35°C, AT 32°C (Min - Max) kW 0,71 —
ET -35°C, AT 38°C (Min - Max) kW 0,65 —
ET -35°C, AT 43°C (Min - Max) kW 0,49 —
ET -30°C, AT 32°C (Min - Max) kW 0,88 —
ET -30°C, AT 38°C (Min - Max) kW 0,85 —
ET -30°C, AT 43°C (Min - Max) kW 0,78 —
ET -25°C, AT 32°C (Min - Max) kW 1,04 —
ET -25°C, AT 38°C (Min - Max) kW 0,99 —
ET -25°C, AT 43°C (Min - Max) kW 0,93 —
Evaporation temperature (Min) °C -35 -20
Evaporation temperature (Max) °C -20 0
Ambient temperature (Min) °C -20 -20
Ambient temperature (Max) °C +43 +43
PS line (Suction) bar 80 80
PS line (Liquid) bar 130 130
Dimension (Width) mm 750 750
Dimension (Height) mm 285 285
Dimension (Depth) mm 590 590
Net weight kg 45 45
Connections (Suction) Inch (mm) 3/8 (9,52) 3/8 (9,52)
Connections (Liquid) Inch (mm) 1/4 (6,35) 1/4 (6,35)
Length of connection piping m 15 15

*The technical data of the NCU-CTC009L05 are tentative.

Panasonic reserves the right to make changes to specifications and data without prior notice.

ET - evaporation temperature, AT - ambient temperature.