9.00kW

OCU-KRC100M08

iCOOL OCU-serien för MT-applikationer

Möjligheten att nå ut till en större målgrupp och täcka den marknad för kondensoraggregat (CDU) som CO₂ ännu inte täcker idag.

Specifikationer

Visa alla
iCOOL OCU-serien - MT
9.00 kW
Model OCU-KRC100M08
Compressors En kompressor
Compatible refrigerants R448A, R449A, R134a, R513A
PED CAT II
Application and nominal cooling capacity MT/LT (kW) MT (9,0)
MT (R449A/R448A) - Cooling capacity at .
ET -15°C, AT 32°C (Min - Max) kW 1,8 - 7,9
ET -15°C, AT 38°C (Min - Max) kW 1,7 - 7,2
ET -15°C, AT 43°C (Min - Max) kW 1,5 - 6,7
ET -10°C, AT 32°C (Min - Max) kW 2,2 - 9,4
ET -10°C, AT 38°C (Min - Max) kW 2,0 - 8,7
ET -10°C, AT 43°C (Min - Max) kW 1,9 - 8,0
ET -5°C, AT 32°C (Min - Max) kW 2,6 - 11,1
ET -5°C, AT 38°C (Min - Max) kW 2,4 - 10,2
ET -5°C, AT 43°C (Min - Max) kW 2,3 - 9,5
MT (R134a/R513A) - Cooling capacity at .
ET -15°C; AT 32°C (Min - Max) kW 1,1 - 4,8
ET -15°C; AT 38°C (Min - Max) kW 1,0 - 4,4
ET -15°C; AT 43°C (Min - Max) kW 0,9 - 4,1
ET -10°C; AT 32°C (Min - Max) kW 1,3 - 5,8
ET -10°C; AT 38°C (Min - Max) kW 1,2 - 5,4
ET -10°C; AT 43°C (Min - Max) kW 1,1 - 5,1
ET -5°C; AT 32°C (Min - Max) kW 1,6 - 7,0
ET -5°C; AT 38°C (Min - Max) kW 1,5 - 6,6
ET -5°C; AT 43°C (Min - Max) kW 1,4 - 6,1
SEPR cooling at ET -10°C AT 32°C 4,29
Annual electricity consumption at ET -10°C AT 32°C kWh/a 13.347
Nominal operating current at ET -10°C MT / -30°C LT AT 32°C and 230 - 400V 50Hz A 7,2
Maximum operating current (in the most loaded phase at 230 - 400V 50Hz) A 9,8
Maximum power consumption kW 5,4
Dimension (Width) mm 1.280
Dimension (Height) mm 963
Dimension (Depth) mm 439
Net weight kg 140
Sound level at 10m dB(A) 41,0
Oil charge dm³ 1,35 + 0,4
Connections (Suction) Inch (mm) 7/8
Connections (Liquid) Inch (mm) 1/2
Liquid receiver dm³ 10,0
Length of connection piping m 40
Maximum height distance (Evaporator above) m 12
Maximum height distance (Evaporator below) m 12
Which pipes needs to be insulated (Suction / liquid / both) Suction
Recommended insulation thickness mm 13
Maximum quantity of evaporators connected Qty. 7
Evaporation temperature (Min) °C -15
Evaporation temperature (Max) °C 10
Ambient temperature (Min) °C -20
Ambient temperature (Max) °C 43
Condenser .
Fans x diameter mm 1x630
Air flow (Nominal) m³/h 6.150
Fan static pressure Pa N/A
Fan power supply V / ph / Hz 200 - 277 / 1 / 50
Fan power consumption W 220
Nominal fan amperage A 1,2
Compressor - additional data .
Compressor model C-8RZ420L4AAL
Volumetric flow m³/h 3,0 - 13,6
Rotation range rps 20 - 90
Current (Full load amperage) A 8,8
Current (Peak current limit / Locked rotor amperage) A 31,9 / —
Oil type FV68S (PVE)
Crankcase heater power consumption W 35
CU power supply .
Voltage V / ph / Hz 3x400 / 50 PE+N (TN-S)
Recommended minimum cable cross-section mm² 5x2,5
Recommended minimum protection C20

Kompletterande produkter